OPERATING MODES

There are two operating modes to select from during set up:
MODE 1
Vacancy sensor (Manual-ON/OFF, Auto-OFF): The user must press the
ON/OFF/DIM button to turn the load ON. The RD-200 keeps the load ON until no
motion is detected for the selected time delay period (adjustable from 15 seconds
to 30 minutes). There is a 30 second reset delay. If motion is detected during this
time, the sensor turns the load back on automatically to the last used dimming
level. After the reset delay time has elapsed, the ON/OFF/DIM button must be
pressed to turn ON the load.
MODE 2
Occupancy sensor (Auto-ON/OFF with manual control and reset
to auto after 5 minutes of vacancy): The load turns ON and OFF automatically
based on occupancy detection. The RD-200 keeps the load ON until no motion is
detected for the selected time delay period. If the load is turned OFF manually,
automatic-ON is re-enabled when no motion is detected for 5 minutes. This
prevents the load from being turned ON after it was deliberately turned OFF.
Time Delay
The time delay can be selected by the user during set up. It can be adjusted
from 15 seconds up to 30 minutes. For additional information on how to adjust
it, please read the SENSOR ADJUSTMENT & PROGRAMMING section of this
installation manual.
Light Level
When the sensor is set for occupancy sensor Mode 2 (Auto-ON/OFF) the light
level feature prevents the sensor from automatically turning the lights ON if
there is already enough light in the area. To adjust the light level, please read the
SENSOR ADJUSTMENT & PROGRAMMING section of this installation manual.
Coverage Area
The RD-200 has a maximum range of 180 degrees
and a coverage area of 600 sq. feet (56 sq. meters).
The sensor must have a clear and unobstructed view
of the coverage area. Objects blocking the sensor's
lens may prevent detection thereby causing the light
to turn OFF even though someone is in the area.
Windows, glass doors, and other transparent
barriers will obstruct
the sensor's view and prevent detection.
INSTALLATION & WIRING
CAUTION — WARNING
To reduce the risk of overheating and possible damage
to other equipment, do not install to control a receptacle,
a motor-operated appliance, a fl uorescent lighting
fi xture, or a transformer-supplied appliance.
Disconnect power to the wall switch box by turning OFF
the circuit breaker or removing the fuse for the circuit before
installing the RD-200, replacing lamps, or doing any electrical work.
1. Prepare the switch box.
After the power is turned OFF at the circuit breaker
box, remove the existing wall plate and mounting
screws. Pull the old switch out from the wall box.
2. Identify the type of circuit.
In a Single Pole Circuit (see Fig. 2), two single wires
connect to two screws on the existing switch. A
ground wire may also be present and connected
to a ground terminal on the old switch. A neutral
wire should also be present in the wall box.
CAUTION - FOR YOUR SAFETY: Connecting a proper ground to the
sensor provides protection against electrical shock in the event of
certain fault conditions. If a proper ground is not available, consult
with a qualifi ed electrician before continuing installation.
Only connect the RD-200 to a Single Pole Circuit. The RD-200 is not suitable
for 3-way switching. If the existing wiring does not match the description for a
Single Pole Circuit, you should consult with a qualifi ed electrician.
3. Prepare the Wires.
Tag the wires connected to the existing switch,
so that they can be identifi ed later. Disconnect
the wires. Make sure the insulation is stripped
off the wires to expose their copper cores to the
length indicated by the "Strip Gage," (in Fig. 3,
approximately 1/2 inch).
www.wattstopper.com/athome
25'
(7.6m)
12'
(3.7m)
Fig. 1: Sensor Coverage Area
HOT (power from
circuit box)
NEUTRAL
LOAD
Ground
(power
to lamp)
Fig. 2: Typical Single Pole
Switch Wiring
Strip Gage
1/2"
12.7 mm
Fig. 3: Wire
Stripping