Lutron PHPM-WBX-DV-WH Instrucciones De Instalación página 3

Ocultar thumbs Ver también para PHPM-WBX-DV-WH:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Load Type Capability
• Incandescent (tungsten)
• Halogen
• Magnetic low-voltage transformer (iron core)
• Electronic low-voltage transformer (solid-state)
• Neon / cold-cathode
• Lutron
Tu-Wire
electronic fluorescent
®
®
dimming ballast
Product Compatibility
The following Lutron
®
control devices for these power modules:
• Lutron
3-wire fluorescent dimmers
®
(except Vierti
dimmers); see approved list in the
®
wallbox lighting controls catalog at www.lutron.com
• GRAFIK Eye
QS control units*
®
• GRAFIK Eye
3000 Series control units*
®
• LP, LCP, GP dimming panels*
• HomeWorks
remote power panels*
®
* Set to fluorescent load type
products may be used as
Test Load for Short-Circuit
• Turn power Off.
• Connect standard switch be tween Line / Hot lead
and the load wire to test circuit.
• Turn power On and check for short or open
circuits.
Line / Hot
Neutral
Wiring
• Provide 12 AWG (2.5 mm
(75 °C minimum) for input power and load circuit.
• Strip 1/2 in (12 mm) insulation from wires before
connecting.
• Run separate neutral for load circuit - no common
neutrals.
• Tighten securely to 7.0 in-lb (0.79 N•m).
Phase-Adaptive Power Module with 3-Wire Fluorescent Input
Switch
Load
2
) copper (Cu) wires
3

Publicidad