LEGRAND Wattstopper DCLV2 Guía De Instrucciones página 3

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

DCLV2 with ELCU-200
The DCLV2 can be used with the ELCU-200 to turn the lights to full ON upon an emergency. The DCLV2 opens the 0-10V circuit at time
of power loss. If the Emergency lighting was in a dimmed state when the normal power was lost, the emergency lighting will be at 100%
versus last dimmed level. The ELCU-200 or some like device needs to be involved in the overall emergency management system to
monitor the loss of normal power so that the 0-10 volt emergency lighting will not only be ON but ON at 100%.
Normal Switched Sense
(Red 18AWG)
Normal Neutral
(White 18AWG)
Normal Power Sense
(Black18AWG)
ELCU-200
Cut jumper loop to use with Normally Closed
test switch, fire alarm panel, security panel, other
White
Neutral
Black
Line
Emergency Power Out
(Red 12AWG)
Emergency Neutral
(White 18AWG)
Emergency Power In
(Black12AWG)
Push
to Test
Red
BZ-XXX
Red
POWER PACK
Control
Typical
Common
3 Wire
Occupancy
+24VDC
Sensor
Violet
Emergency
Lighting
Gray
LOAD 1
0-10VDC Dimming
Ballast Required
Emergency Line
Emergency Neutral
L
o
a
Switch
d
(optional)
Violet
Gray
3
Relais externe 1
+24VDC
Common
DCLV2
0-10V
0-10V
Control
Ground
Ground

Publicidad

Tabla de contenido
loading

Tabla de contenido