Mounting support legs "V" version
Ø 500 - 630 - 710 mm models
Installation
Minimum distance from walls
"V" Version
(top view)
1,5 m
Extended support legs 1,2 m are required.

Electric Connections

Before carrying out maintenance or other operations on unit
ensure that the main disconnecting switch has been opened.
1. Earth model by using the stud that is located under the
front cover (refrigerant connection side), for the removal
instructions go to section "Removal of mobile parts".
2. Electric connections must be carried out in the fan motor
terminal boxes according to provided scheme.
3. Check that voltage and the frequency scheme are in com-
pliance with those stated on unit name-plate.
4. Predispose a disconnecting switch and all other protection
devises imposed by local legislation, dimensioned accor-
ding to the indications of the data tables and the connec-
tions schemes.
44
www.modine.com
Ø 800 - 910 - 1000 mm models
Min. distance between models with double row motors
"H" Version
Minimum distance between
models in open field.
1,5 m
0,8 m
Minimum distance between models
in the presence of walls.