Set Temperature - Danfoss AK-CC 210B Manual Del Usuario

Ocultar thumbs Ver también para AK-CC 210B:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 12
The buttons
Set menu
1. Push the upper button until a parameter
r01 is shown.
2. Push the upper or the lower button and
find the parameter you want to change.
3. Push the middle button until the
parameter value is shown.
4. Push the upper or the lower button and
select the new value.
5. Push the middle button again to enter
the value.
Cut-out alarm relay / receipt alarm/see alarm
code
• Push the upper button shortly
Fault code display
E 1
Fault in controller
E 6
Change battery + check clock
E 27
S5 sensor error
E 29
Sair sensor error
E 64
Sc sensor error
Factory setting
If you need to return to the factory-set values, do the following:
- Cut off the supply voltage to the controller
- Keep upper and lower button depressed at the same time as you recon nect the supply voltage
© Danfoss | DCS (vt) | 2021.03

Set temperature

1. Push the middle button until the
temperature value is shown.
2. Push the upper or the lower button and
select the new value.
3. Push the middle button to select the
setting.
Reading the temperature at defrost sensor
• Push briefly the lower button.
Manual start or stop of a defrost
• Push the lower button for four seconds.
(However, not application 4).
Alarm code display
A 1
High temperature alarm
A 2
Low temperature alarm
A 4
Door alarm
A 5
Max. Hold time
A 15
DI 1 alarm
A 16
DI 2 alarm
A 45
Standby mode
A 59
Case cleaning
A 61
Condenser temperature alarm
A 80
Condenser blocked alarm
AA 4
Service request alarm
LED
Light Emitting Diode
= refrigeration
= defrost
= fan running
Flashes fast at alarm
Status code display
S0
Regulating
S 1
Waiting for end of the coordinated defrost
S 2
ON-time Compressor
S 3
OFF-time Compressor
S 4
Drip-off time
S 10
Refrigeration stopped by main switch
S 11
Refrigeration stopped by thermostat
S 14
Defrost sequence. Defrosting
S 15
Defrost sequence. Fan delay
S 17
Door open (open DI input)
S 20
Emergency cooling
S 25
Manual control of outputs
S 29
Case cleaning
S 32
Delay of output at start-up
S 34
Condenser blocked event active
non
The defrost temperature cannot be
displayed. There is stop based on time
-d-
Defrost in progress
PS
Password required
AN33481406482302-000201 | 5

Publicidad

Tabla de contenido
loading

Tabla de contenido