Adapting The Unit To The Mains Voltage - Pfannenberg DTS Serie Instrucciones De Servicio

Ocultar thumbs Ver también para DTS Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 241
ENG
4.6.7

Adapting the unit to the mains voltage

Factory settings control transformer
Fig. 16: Adapting the mains voltage on the control transformer
Units with a rated voltage of 400 / 460 V can be optionally connected to another mains voltage.
The mains voltage on the transformer must be adapted for this.
The adaption is made by replugging the supply cable on the primary side of the transformer.
The upstream fuse must correspond to the changed mains voltage, see column
The data for the transformer factory settings can be found on the yellow connection diagram (1) on the rear of the unit.
UL-conform
Mains voltage
50 Hz
60 Hz
400 V
460 V
Tab. 7: Transformer options and upstream fuse
Operating Manual | Attachment and Installation Cooling Units | Standard Controller (SC) – 400 / 460 V, 3~ | 086100009e
:
y "
",
Transformer
Input winding
T1/ 1 [0] – T 1/ 4 [400]
T1/ 1 [0] – T 1/ 7 [460]
Input winding control transformer
"upstream fuse" in
-blow, suitable for transformer protection.
Tab. 7
Upstream fuse
(min. 480 V)
Max. 4 A
Max. 2.5 A
39/60