Adapting the unit to the mains voltage

Factory settings upstream transformer
Fig. 26: Adapting the mains voltage on the upstream transformer
Units with a mains voltage of 400/460 V can be connected optionally to another mains voltage.
The mains voltage on the upstream transformer must be adapted for this.
The adaption is made by replugging the supply cable on the primary side of the transformer.
The upstream fuse must match the changed mains voltage, see the "Upstream fuse" column in
The data for the transformer factory settings can be found on the yellow connection diagram (1) on the rear of the unit.
UL-conform with following fuses: Category "Class CC", slow-blow, suitable for transformer protection.
Mains voltage
400 V
440 V
460 V
Tab. 9: Transformer options and upstream fuse
NOTE
The changed mains voltage on the transformer must be marked on the yellow connection diagram (1) on the back of the unit.
Operating Manual | Roof-mounted Cooling Unit | Multi Controller (MC) – 400 V, 2~ | 086100031c
Transformer input winding
T1/ 1 [0] – T 1/ 2 [400]
T1/ 1 [0] – T 1/ 3 [440]
T1/ 1 [0] – T 1/ 4 [460]
Input winding upstream transformer
Tab. 9
Upstream fuse (min. 480 V)
DTT 6201
Max. 5 A
Max. 5 A
Max. 5 A