Dts Cooling Unit Assembly (Side Attachment) - Pfannenberg DTS Serie Manual De Instrucciones

Ocultar thumbs Ver también para DTS Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 234
ENG
4.5.2

DTS cooling unit assembly (side attachment)

4.5.2.1
Making cut-outs for DTS cooling unit
Assembly holes
Fig. 9: External view of switch cabinet, assembly bores and cut-outs
1
Holes
2
Device contour
Requirements
DANGER – Danger to life due to electric shock. Make sure that the unit is voltage-free.
All general requirements are satisfied, see "General", Page 25.
Required tools and materials
Saw
Switch cabinet milling machine if necessary
Protective covers
Procedure
1.
Ensure that the switch cabinet has a protective cover to protect against chips.
2.
Make cut-outs and assembly holes as shown in Fig. 9.
3.
Deburr the cutting edges.
4.
Remove chips and assembly waste from the switch cabinet.
The cut-outs and holes are made and the cooling unit can be assembled.
Operating Manual | Attachment and Installation Cooling Units | Standard Controller (SC) – 230 V | 086100001e
Assembly cut-outs
3
Assembly cut-outs
26/58

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Dti 6201 serieDti 6301 serie

Tabla de contenido