Adapting the unit to the mains voltage

Factory settings upstream transformer
Fig. 16: Adapting the mains voltage on the upstream transformer
Units with a rated voltage of 400 / 460 V can be optionally connected to another mains voltage.
The mains voltage on the upstream transformer must be adapted for this.
The adaption is made by replugging the supply cable on the primary side of the transformer.
The upstream fuse must correspond to the changed mains voltage, see column
The data for the transformer factory settings can be found on the yellow connection diagram (1) on the rear of the unit.
UL-
Mains voltage
400 V
440 V
460 V
Tab. 7: Transformer options and upstream fuse
NOTE
The mains voltage changed on the transformer must be marked in the yellow connection diagram (1) on the rear of the unit.
Operating Manual | Attachment and Installation Cooling Units | Standard Controller (SC) – 400 V, 2~ | 086100003e
:
y "
Transformer input
winding
T1/ 1 [0] – T 1/ 2 [400]
T1/ 1 [0] – T 1/ 3 [440]
T1/ 1 [0] – T 1/ 4 [460]
Input winding upstream transformer
",
-blow, suitable for transformer protection.
Upstream fuse (min. 480 V)
DTx 6201
Max. 4 A
Max. 4 A
Max. 4 A
"upstream fuse" in
Tab. 7
DTx6301
Max. 6 A
Max. 6 A
Max. 6 A
39/60