NOTE: In some cases, not all leads will be used.
Cap off unused wire.
3. Feed excess wire into junction box and secure back
plate to junction box. (See Figure 1)
4. Snap in arrows on EXIT panel as required. Then snap
EXIT panel to housing: top first, then bottom. (See Figure 1)
NOTE: Use flexible
conduit only.
(See Figure 4)
SIDE MOUNTING
1. Attach crossbar to junction box. Set the crossbar so
longer blade is touching junction box. (See Figure 5)
Figure 5
Plastic
Housing
EXIT Panel
Directional Arrow
2. Open the EXIT housing.
(See Figure 6) Feed the
transformer input leads
through side hole, being
sure to secure wire into wire
guides molded at edges of
the sign. (See Figure 5)
3. Attach sign to canopy by inserting canopy into sign
at an angle, then twisting to secure. (See Figure 5)
4. Feed transformer input leads through center hole
and make the proper connections. (See Figures 2-3)
NOTE: If using 120VAC, connect black and white
leads to building utility.
NOTE: If using 277VAC, connect orange and
white leads to building utility.
If the unit is self-powered, be sure to snap battery
connector together.
5. Feed excess wire into junction box and align holes in
canopy with holes in crossbar. Use screws supplied
to tighten canopy to crossbar so canopy is securely
fastened and tight against wall. (See Figure 5)
PAGE 2 OF 9
INSTALLATION CONTINUED
Figure 4
Back Plate
Canopy
Wire Nuts
Diffuser
Crossbar
Snap-in
Crossbar Screws
(not included)
Figure 6
6. Snap in arrows to EXIT panel as required. Then snap
EXIT panel to housing: top first then bottom.
CEILING MOUNTING
1. Attach crossbar to junction box. Set the crossbar so
the longer blade touches junction box.(See Figure 7)
Figure 7
Plastic Housing
Junction
Box
EXIT Panel
2. Open the EXIT housing. (See Figure 6) Feed the
transformer input leads through top hole, being
sure to secure wire into wire guides molded at
edges of sign.
3. Attach sign to canopy
by inserting canopy
into sign at
an angle. Twist to
secure. (See Figure 8)
4. Feed transformer
input leads through
center hole and
make the proper
connections. (See Figures 2-3)
NOTE: If using 120VAC, connect black and white
leads to building utility.
NOTE: If using 277VAC, connect orange and
white leads to building utility.
If the unit is self-powered, be sure to snap battery
connector together.
5. Feed excess wire into junction box and align holes
in canopy to crossbar so that canopy is securely
fastened and tight against the ceiling.
6. Snap in arrows to EXIT panel as required. Then snap
EXIT panel to housing: top first, then bottom.
Junction Box
Crossbar
Canopy
Snap-in
Directional Arrow
Figure 8
Diffuser
Canopy
0621 IH-6509