Testing the battery back-up

□ Push the test button on the side of the exit sign housing (A) after charging the battery for 24 hours.
□ The red AC indicator on the bottom of the exit sign housing (A) should turn off.
□ When the test button is released, the red AC indicator on the bottom of the exit sign housing (A) should illuminate again.
nOTiCe: The battery supplied with the exit sign requires no maintenance. However,
NEC and NFPA code regulations require that routine tests be performed. Once every
month, the battery back-up needs to be tested by holding in the test switch for the
duration of 30 seconds Once every 12 months, a full 90 minute test (per UL requirements)
needs to be performed by disconnecting power to the sign and leaving it in emergency
mode. The LEDs should remain on for a minimum of 90 minutes.
nOTe: The battery supplied in this exit sign has a life expectancy of 5 years
when used in a normal ambient temperature of 72°F.

Care and Cleaning

CaUTiOn: Before attempting to clean the fixture, disconnect the power to the fixture by turning the breaker off or removing the fuse from
the fuse box.
□ Clean the fixture with a soft, dry cloth.
□ Do not use cleaners with chemicals, solvents, or harsh abrasives.
□ Do not use liquid cleaner on the LEDs, LED driver, or wiring inside the light fixture.

Troubleshooting

Before doing any work on the fixture, disconnect power to the light fixture.
WarninG:
Minor problems often can be fixed without the help of an electrician.
Problem
Possible Cause
The fixture will not light.
The power is off.
The circuit breaker is off.
There is a bad connection.
There is a defective switch.
The fuse blows or the circuit breaker
The wires are crossed or the power
trips when the light is turned on.
wire is grounding out.
Test Button
AC Indicator
Solution
Ensure the power supply is on.
Ensure the circuit breaker is in the on position.
Check to ensure proper wire connections are made.
Contact a qualified electrician.
Contact a qualified electrician.
Check the wire connections.
Contact a qualified electrician or call customer
service 1-855-384-7754.
8
GUide d'UTiLisaTiOn eT d'enTreTien
enseiGne de sOrTie À deL
Questions, difficultés, pièces manquantes?
Téléphonez au service à la clientèle de ETiSSL
8 h - 17 h, HNC, du lundi au vendredi.
1-855-ETI-SSLI (1-855-384-7754)
www.ETiSSL.com
Nous apprécions la confiance que vous avez accordé à la ETi Solid State Lighting, Inc. en achetant ce luminaire à DEL.
Consultez notre gamme complète de produits en ligne pour satisfaire vos besoins en produits d'amélioration du foyer.
Nous vous remercions d'avoir choisi ETi!
n° de commande 55301101
n° de pièce eM-eX-r
n° de certification 55301101
MERCI
55301102
eM-eX-G
55301102

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

55301102Em-ex-rEm-ex-g

Tabla de contenido