Initial configuration

The first time the unit is powered up, it will enter into the Wizard mode. The display will show the message
flashing with 0.
Step 1:
Select the most suitable InI option based on the type of installation to be carried out and press SET. The
available options will be shown in the following table:
Type of installation
InI
Cold regulation
0
Demo Mode: it displays the temp. but does not regulate or activate relays
1
Solenoid
3
Solenoid + compressor
4
Solenoid
6
Solenoid + compressor
11
Solenoid
13
Solenoid + compressor
Note: Additional quick set up choices, including hot gas and reversed cycle options are detailed in the User Manual.
Step 2:
Use keys
and
to enter the desired Temperature Set Point value and press SET. The wizard has finished.
The unit will begin to regulate the temperature.
If this is not the first time you use the wizard, after completing the last step the display will show the
message dFp (default parameters). You may choose between two options:
0: Only parameters included in the wizard will be modified
1: Parameters modified by the wizard will be changed, all other parameters will return to their factory setting.
Important: The wizard will start automatically only on the first power on. To enter the wizard mode, initiate Stand-By mode by pressing
the
key for 3 seconds and wait until the unit completely halts the temperature regulation
(The
indicator will light up permanently) and press the following keys in sequence,
Wizard parameters list
o00
Configuration of relay AUX1
I00
Connected probes
I10
Configuration of digital input 1
I11
Polarity of the digital input 1
I20
Configuration of digital input 2
I21
Polarity of the digital input 2
d1
Maximum defrost duration (0=defrost deactivated)
d7
Type of defrost
F3
Status of the fans during the defrost
For more details, full User Manual and other information, scan the QR code.
© Danfoss | DCS (vt) | 2021.02
Defrost
Evaporator fans
o00
Electric
Yes
Electric
Yes
Air
Yes
Air
Yes
Static
No
Static
No
0=Deactivated
2=Light
1=Probe 1 (Cold room)
0= Deactivated
3=Severe external alarm
6=Defrost block
0=Activates on closing contact
0= Deactivated
3=Severe external alarm
6=Defrost block
9=High pressure switch for Hot Gas 10=Remote Stand-by
0=Activates on closing contact
0=Resistors
3=Reversal of cycle
0=Shut down
Parameters
I00
I10
I11
I20
0
2
0
0
1
2
0
0
0
1
0
0
1
1
0
0
0
1
0
0
1
1
0
0
,
1=Compressor/Crankcase heater
3=Virtual control
2=Probe 1 (Cold room) + Probe 2 (Evaporator)
1=Door contact
4=Change of SP
7= Low pressure switch
1=Activates on opening contact
1=Door contact
4=Change of SP
7=Register probe
1=Activates on opening contact
1=Air/fans
1=Running
I21
d1
d7
F3
0
0
20
0
0
0
20
0
0
0
20
1
0
0
20
1
0
0
20
1
0
0
20
1
, SET.
2=External alarm
5=Remote defrost
8=Remote Stand-by
2=External alarm
5=Remote defrost
8=Probe 2° evaporator
2=Hot gas
AN36292867744601-000101 | 3
Diagram to
be used
0
A
0
B
1
A
1
B
-
A
-
B