GRAFIK Systems
TM
Installation Instructions
Occupant Copy
Please refer to the enclosed CD for the product
Specification Sheets and Operation Manuals,
Ethernet Device IP program, and RS232 and Ethernet
Protocol information.
Mounting
1. Mount the Control Interface directly on a wall, as
shown in the Mounting Diagram, using screws (not
included). When mounting, provide sufficient space for
connecting cables.
The unit can also be placed in the LUT-19AV-1U AV
rack using the screws provided with the unit. The
LUT-19AV-1U will hold up to four units.
If conduit is desired for wiring, the LUT-5x10-ENC can
be used to mount one unit.
2. Strip 4 in (10 mm) of insulation from wires. Each Data
Link terminal will accept up to two 18 AWG
(1.0 mm
2
) wires.
3. Connect wiring as shown in the Wiring Diagram
(next page). LED 1 lights continuously (Power)
and LED 7 blinks rapidly (Data Link RX) when the
2.50
SELV / PELV / NEC
Class 2 Data Link is installed
®
correctly.
Dimensions
3.75
5.26
1.06
3.75 in
(95 mm)
1.0 in
(27 mm)
Control Interface
SELV / PELV / NECR Class 2
Please Read
2.5 in
(63 mm)
4.26
5.26 in
(137 mm)
For California residents only:
The batteries in these devices (GRX-CI-PRG, GRX-IA-CI-PRG, and
®
QSE-CI-NWK-E) contain Perchlorate Material – special handling may apply.
For more information visit www.dtsc.ca.gov/hazardouswaste/perchlorate
GRX-CI-PRG, GRX-IA-CI-PRG,
GRX-CI-NWK-E, GRX-CI-RS232,
GRX-IA-CI-NWK-E, GRX-IA-CI-RS232,
OMX-CI-NWK-E, OMX-CI-RS232
QSE-CI-NWK-E
Mounting Diagram
Wall
Control Interface
Mounting
Holes
4.25 in
(108 mm)
12 V- 125 mA
or
24 V- 65 mA
24-36 V- 65 mA
LUT-19AV-1U
LUT-5x10-ENC
Wire Strip Length
3/8 in
(10 mm)
Mounting Hole Detail
0.25 in
(6 mm)
0.1875 in
(5 mm) dia.
0.3125 in
(8 mm) dia.
0.1875 in
(5 mm) dia.
#6 or #8 (M3 or M4)
screw recommended
(not included)