Eaton Greengate LK 16 Manual De Instalación página 3

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

4.
Document relay to circuit information for future
reference.
Relay Wiring
Wire: 10 AWG Max.
Relay Rating: 20Amps, 277V
Standard Relay Card Wiring
Latching Relay Card Notes
1.
The Latching Relay Card is rated for single-pole load use
only. Connection of 2 pole circuits/loads to the Latching
Relay Card will void the equipment warranty and may
result in severe injury or death, and/or damage to the
equipment.
2.
Relay ratings are 120/277/347 volt, 20 amp maximum.
3.
Relay terminal blocks have a maximum limit of 6 AWG
wire.
Latching Relay Card Wiring
The latching relay is a simple closure, breaking the line and
load wires of a normal circuit. To wire the relay into the
control circuit:
1.
Connect a 120, 277 or 347 volt, 20 amp maximum,
de-energized branch circuit breaker to the relay terminal
block.
2.
Connect the load wiring to the output terminal block.
Terminal blocks are not polarity sensitive although it
N
ote:
is recommended that line and load be brought into
terminal blocks in the same manner for consistency.
3.
Tighten down relay terminal screws. Manufacturer's
recommended torque rating is 18 lb-in. (1.475 foot-lbs)
(2.0 Nm).
LiteKeeper 16/32 Enclosure
4.
Document relay to circuit information for future
reference.
From Brand Circuit
To Lighting Load
Modular Relay Card Notes
The Modular Relay Card provides flexible options for relay
control. It is designed to allow modular relay control by
allowing you to install a variety of relay module types on
the same relay card. Current available relay module types
include a Two Pole Relay Module (TPRM) Normally Open,
the Latching Relay Module (LRM) and the Standard Relay
Module (SRM).
Standard Relay Module
1.
The Standard Relay Module is rated for single-pole
load use only. Connection of 2 pole circuits/loads to
the Standard Relay Module will void the equipment
warranty and may result in severe injury or death, and/
or damage to the equipment.
2.
Relay ratings are 120 or 277 volt, 20 amp maximum.
3.
Relay terminal blocks have a maximum limit of 10AWG
wire.
Relay Wiring
Wire: 6 AWG Max.
Relay Rating: 20Amps, 347V
K8
U2
U3
K6
U1
RN1
RP1
RP2
K4
Q1
Q2
LED1
K2
SR1
Latching Relay Card Wiring
TPRM
Line
Load
Line
Load
Relay Wiring: 20Amps
208/240/480 VAC
Wire: 6 AWG Max.
Modular Relay Card
Connecting Relay Loads
TB8
From Brand Circuit
MOV8
To Lighting Load
TB6
MOV6
TB4
MOV4
MOV2
TB2
LRM
Line
Load
Relay Wiring: 20Amps
120/277/347 VAC
Wire: 6 AWG Max.
SRM
Line
Load
Relay Wiring: 20Amps
120/277 VAC
Wire: 10 AWG Max.
3

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Greengate lk 32

Tabla de contenido