ENG
3.4.9

Energy-saving mode

Fig. 10: Temperature sensor - TS2
Cooling units with Multi-Controllers (MC) are equipped with an energy-saving module.
The Multi-Controller (MC) therefore has a connection for a second TS2 temperature sensor (1).
The TS2 temperature sensor (1) is installed externally on the cooling unit and monitors the switch cabinet interior temperature.
Functional description:
In the delivery condition, the energy-saving mode is activated when cooling mode is not activated for 30 minutes. The
control panel then shows "En", see section "Controller", Page 17.
If the switch cabinet interior temperature exceeds the temperature setpoint during active operation, a cooling request is
sent and the energy-saving mode is interrupted.
The cooling mode always remains active until the temperature setpoint minus hysteresis is reached. The energy-saving
mode is always activated 30 minutes after reaching the temperature setpoint.
If the external TS2 temperature sensor (1) measures a drop below the temperature setpoint in the energy-saving mode,
the evaporator fan (internal) switches off. The temperature setpoint is measured minus the hysteresis.
If the external TS2 temperature sensor (1) measures exceeding of the temperature setpoint, the evaporator fan (internal)
switches on. The value of the temperature setpoint is measured plus hysteresis.
If no fault occurs, the fault indication output in energy-saving mode is closed.
NOTE
For details about the electrical connection, see chapter "External temperature sensor TS2", Page 47.
Operating Manual | Roof-mounted Cooling Unit | Multi Controller (MC) – 400 V, 2~ | 086100031c
23/80