AREO i
- Heat exchanger, made up of copper piping and aluminium fins provi-
ding superior thermal conductivity compared with traditional iron pipe
exchangers.
The coil is placed to the rear compared with the air outlet; on the front
there is an auxiliary drip tray that guarantees total collection of conden-
sate.
- Condensate drip tray in galvanized steel, insulated with closed cell
polyurethane, connected to the auxiliary tank.
- Electric motors:
Two permanent magnets with built-in inverter
A)
230V-50/60HZ or 400V-3-50/60 HZ power supply
1)
passive power factor correction circuit
2)
0-10V Control signal
3)
Electronics and motors protected from overheating
4)
Alarm relay
5)
Low voltage supply detection
6)
Motor current control
7)
Gradual start (soft starter)
8)
Max air temp 70°C
All motors are fitted with an internal safety thermal cut-out, produced with
an IP 44 protection rating.
- Axial fan with statically balanced sickle blades housed in a specially
designed compartment that enhances ventilation and reduces noise
emissions.
- Safety grille made of electro galvanized steel wire: it supports the motor
and is fixed to the cabinet by means of vibration-damping supports.
Main components as shown in figure 2:
(1)
Cabinet: side panel
(2)
Cabinet: upper/lower panel
(3)
Rear panel/fan nozzle
(4)
Finned block heat exchanger (heat exchanger coil)
(5 )
Safety grille (fan) supporting motor
(6)
Adjustable louvers
(7)
Auxiliary water drip tray
(8)
Main water drip tray
(9)
Top cover of heat exchanger
(10)
Air conveyor duct
(11)
Wall/ceiling mounting brackets
(12)
Plastic corner trim on cabinet
4
DIMENSIONS
Figure 3 shows the dimensions of the unit:
(1)
Water inlet connection, male gas coupling
(2)
Water outlet connection, male gas coupling
(3)
Condensate drain coupling
5
INSTALLATION
Remove the fan heater from the packing container and check that no
damage has occurred during transport.
Before starting to install the unit, make sure that the installation height and
air range conform to the specifications provided in the technical catalogue.
The maximum installation height is shown in figure 4.
All models making up the AREO series can be mounted either on a wall
(heating function) or on the ceiling (heating function ONLY).
In the case of wall installation, use suitable mounting boards, available
as accessories:
DFP for wall mounting
DFC for mounting on columns
Adjustable DFO for mounting on walls/columns (from 0° to ±45°).
If you do not use the mounting boards supplied by the manufacturer, make
sure in any case that the unit is adequately spaced from the wall or ceiling,
at a distance that is at least that shown in figure 5.
Use screw anchors of adequate dimensions to support the weight of the
unit and make sure that the surface of the installation site is suited to the
purpose.
For ceiling installation, use the 4 brackets provided and suspend the fan
heater with 4 suitable chains, bearing in mind its weight.
To optimise the distribution of air within the room, half of the louvers
should be turned 180° as indicated in figure 6, by pressing on the louver
to compress the spring.
Use suitable lifting equipment to move the unit to the installation site and
rest it on the side of the fins.
È severamente vietata la riproduzione anche parziale di questo manuale / All copying, even partial, of this manual is strictly forbidden
The plumbing connections on the side of the unit may not be used to carry
or bear the weight of the unit.
The unit must be installed perfectly level to prevent air pockets from forming
within the heat exchange coil, and in the case of operation in the cooling
phase, to ensure proper drainage of the condensate.
Warning: for hydraulic connections use a tightening wrench
to avoid the manifold rotation that may damage the heat
exchanger (figure 7)
When used in air conditioning mode there should be an adequately sized
condensate drain line (with sufficient inclination), ensuring its operation
is tested before starting the unit.
In order to prevent dragging condensate phenomena use
the AREOi fan heaters in the cooling phase only at the maximum
speeds permitted for each model. The maximum permitted speed
for each model may be found in the technical manual or the
selection program (it corresponds approximately to 45% of the
maximum value). To limit such speed (during air conditioning)
appropriately programme the MYCOMFORT LARGE controller
(see relative parameter in the operating manual)
Warning: cooling operation is ONLY allowed for WALL-
MOUNTED units
The water inlet must be placed in correspondence with the lower fitting,
in order to have improved air ventilation inside the coil and a correct
functioning of the heat exchanger.
If the unit is to be ceiling mounted (for vertical air flow), make sure it is
installed in a perfectly level position.
On completing installation, open and direct the louvers.
6
WIRING
The standard motors used on the AREO i fan heater series consist of two
permanent magnets with built-in inverter.
THERE IS NO NEED FOR AN EXTERNAL THERMAL PROTECTION,
THE ENGINE HOWEVER REQUIRES PROTECTION OF ITS POWER
SUPPLY LINE.
Make the electrical connections with the power supply disconnected, in
accordance with current safety regulations. All wiring must be carried out
by qualified personnel.
Check that the mains electricity supply is compatible with the voltage
shown on the unit rating plate.
Scrupulously follow the wiring diagram provided, according to the type
of installation.
Each fan heater on the supply line must be equipped with an omni-
polar mains disconnecting switch pole in overvoltage category III.
The table in figure 8 shows the electrical specifications of the motors, where:
SPEED
Number of motor revolutions (Max)
POWER SUPPLY
Power supply voltage
I
Electrical power consumption
IN
P
Absorbed current
IN
-
For further information or communication, please contact the
company at: info@galletti.it
7
EN