3
Night setback No /
Temp. range
Start
Stop
Select:
Cursor
F1
Night setback No /
Temp. range
Start
Stop
Main menu:
Room
Cool
Mode
44
Night setback
Yes
19
- 28
23:00
5:00
Content
F2
F3
F4
Night setback
Yes
19
- 28
23:00
5:00
Changes saved
Fri
Set temp.
Auto
Temp.
Fan
Move the cursor to the desired item with the F1 or
F2 button out of Night setback No (disable)/Yes
(enable), Temp. range, Start time, or Stop time.
Change the settings with the F3 or F4 button.
Temp. range: The lower limit temperature (for
•
heating operation) and the
upper limit temperature (for
cooling operation) can be set.
The temperature difference
between the lower and upper
limits must be 4ºC (8ºF) or
more. The settable temperature
range varies depending on the
connected indoor units.
* 1ºC increments
Start/Stop time: settable in 5-minute increments
•
* Press and hold the button to rapidly advance
the numbers.
Press the SELECT button to save the settings.
A confirmation screen will appear.
Navigating through the screens
• To go back to the Main menu .......... MENU button
• To return to the previous screen ...... RETURN button
will appear on the Main display in the
Full mode when the Night setback function is
enabled.
appears when the timer is disabled by the
centralized control system.
The Night setback will not work in the following cases:
when the unit is in operation, when the Night setback
function is disabled, during an error, during check (in the
service menu), during test run, during remote controller
diagnosis, when the clock is not set, during Function
setting, when the system is centrally controlled (On/Off
operation, temperature setting, or Timer operation from
local remote controller is prohibited).