INSTALLATION
PROCEDURES

Unpacking Precautions

The unit is shipped bolted to its mounting pad, ready for
hookup. Use care to avoid damage from dropping, bumping,
collision, etc. Store and unpack carton with the proper side
up, as noted on the shipping carton.

Delivery Inspection

After removing the carton, carefully inspect the Home
Generator and Automatic Power Transfer Switch
components for any damage that may have occurred during
shipment.
IMPORTANT: If loss or damage is noted at time of
delivery, have the person(s) making delivery note all damage
on the freight bill and affix his signature under the
consignor's memo of loss or damage. If loss or damage is
noted after delivery, separate the damaged materials and
contact the carrier for claim procedures. Missing or
damaged parts are not warranted.

Shipment Contents

The Home Generator System is supplied with:
• Backup Power generator
• Pre-attached mounting pad
• Automatic Power Transfer switch
• One 24" flexible hook-up pipe
• Installation and start-up manual (P/N 191186)
• Owner's manual(P/N 191187)
• Product warranty sheet (P/N 190881)
• Installation checklist (P/N 190840)
• Three access door keys
• Four lifting hole plugs
• Oil fill spout
• Touch-up paint
• One spare 15A fuse
• Diagnostic LED kit (diode/plate/decal/pin connectors (2))

Required Tools/Equipment

• Two 48" lengths of 1" OD pipe (NOT conduit)
• Hole punches for 16ga steel
• Torque screwdriver, 5 to 50 inch-pound range
Briggs & Stratton Power Products Home Generator System
Installation Manual

Home Generator System Location

TO THE INSTALLER: Consult with the owners
and convey any technical considerations that might
affect their wishes, before applying these general
guidelines.
Generator Clearances
The generator enclosure must be a minimum of 3 ft.
(92 cm) from combustible material (NFPA 37). Leave at
least 3 ft. (92 cm) all around the enclosure for access to the
inside of the enclosure (NEC Art. 110-26a, Art. 110-26b).
The unit's exhaust port must be at least 5 ft. (152 cm) from
any building opening (window, door, vent etc.), and the
exhaust must not be able to accumulate in any occupied
area (Figure 1).
Figure 1 — Home Generator System Clearances
Exhaust
Port
General Location Guidelines
• Install the unit outdoors ONLY. NO MODIFICATIONS
WILL ALLOW INSIDE INSTALLATION!
Place the unit in a prepared location that is flat and has
provisions for water drainage.
• Install the unit where air inlet and outlet openings will
not become obstructed by leaves, grass, snow, etc. If
prevailing winds will cause blowing or drifting, you may
need to construct a windbreak to protect the unit.
• In locations where strong winds blow from one
direction, face the generator air inlet openings into the
prevailing winds, if possible.
4
Exhaust port must be
5 ft (152 cm) minimum
distance from building
openings