WIRING
1. To connect the power to the heater, simply remove
the screw from the front of the unit. This allows the
hinged bottom to open, providing access to the
electrical wiring and connectors. (See Figure 5)
2. Attach the cable connectors to the unit and slide
the 10 gauge or thicker wire through the cable
connector. (See Figure 1)
3. Pull enough wire through the connector to work with
when making the connections.
NOTE: Wiring compartment volume: 370 in
4. Connect the wire to the power terminal block
located in the base of the heater (See Figure 6).
NOTE: Unit is 240/208 volts. When wiring a two
conductor cable with ground, the white wire
must be marked black by adding a piece of
black electrical tape to the wire near the point
of connection.
NOTE: To decrease the heat output of the
heating unit, see Adjusting Heat Output below
and Figure 7.
WARNING! To prevent possible electric shock,
disconnect power to the heater at the main
service box before attempting to adjust the
heat output of this unit.
ADJUSTING HEAT OUTPUT
Heat output can be increased or decreased by switching
wires at the wattage change terminal board. The H-6517
is factory wired to deliver a heat output of 17,065 BTU per
hour. The H-6518 is factory wired to deliver a heat output
of 25,598 BTU per hour. For less heat output, refer to the
Heat Output Adjustments table and change the wires at
the wattage change terminal board as shown in Figure 7.
PAGE 5 OF 21
INSTALLATION CONTINUED
Bottom
View
Power
Terminal Block
Black
White
Green or
Copper
HEAT OUTPUT ADJUSTMENTS FOR H-6517
BTU/HR
VOLTS
17,065
14,215
11,365
8,533
12,799
.
3
10,659
8,533
6,396
Figure 6
HEAT OUTPUT ADJUSTMENTS FOR H-6518
BTU/HR
VOLTS
25,598
21,331
17,065
12,799
19,198
15,990
12,799
9,598
RD
GROUND
MAX FUSE
WATTS
SIZE
240
5000
30
240
4165
25
240
3332
20
240
2500
15
208
3750
25
208
3123
20
208
2500
15
208
1874
15
MAZ FUSE
WATTS
SIZE
240
7,500
45
240
6,250
35
240
5,000
30
240
3,750
20
208
5,625
40
208
4,685
30
208
3,750
25
208
2,812
20
1
HI
2
LIMIT
3
YL
4
ELEMENT
BLU
5
FAN
6
CONT.
BLK
WATTAGE CHANGE
TERMINAL BOARD
C D
A B
THERMOSTAT
ALARM LIGHT
POWER
TERMINAL
BLOCK
L1
L2
FIELD
WIRING
MOVE
JUMPERS
HEATER
FROM C-D TO
AMPS
A-B
20.9
None
17.4
Blue
Blue and
13.9
Yellow
Blue, Yellow
10.4
and Red
18.0
None
15.0
Blue
Blue and
12.0
Yellow
Blue, Yellow
9.0
and Red
MOVE
JUMPERS
HEATER
FROM C-D TO
AMPS
A-B
31.3
None
26.1
Blue
Blue and
20.9
Yellow
Blue, Yellow
15.7
and Red
27.1
None
22.3
Blue
Blue and
18.1
Yellow
Blue, Yellow
13.6
and Red
Figure 7
7
8
9
10
11
12
FAN
MOTOR
0521 IH-6517