Toshiba TCB-CC163TLE Manual De Instalación página 12

Ocultar thumbs Ver también para TCB-CC163TLE:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 110
DIPSW1
Zone address switches
Use these to set the zone addresses.
1(Central control Adress 1-16)
2(Central control Adress 17-32)
3(Central control Adress 33-48)
4(Central control Adress 49-64)
ON-OFF controller main/sub selection switch
This is normally used at the main (OFF) setting.
When the ON-OFF controller is to be used by a main unit
and a sub unit (2 units) in one zone, set one unit to main
(OFF) and the other unit to sub (ON).
OFF: ON-OFF controller operates as main controller.
ON: ON-OFF controller operates as sub-controller.
• Set the zone address switch of the sub ON-
NOTE
• One ON-OFF controller must always be set as
Central control main/sub selection switch
(OFF: main, ON: sub)
This is normally used at the main (OFF) setting.
Set it to sub (ON) when a communication adapter, ON-OFF
controller is to be used concurrently.
Group inhibited/all indoor unit control permitted selection
switch
Use these to switch between the group inhibited and all
indoor unit control permitted statuses for each of the four
groups.
All indoor unit control permitted
1-16 Group inhibited
5-16 Group inhibited
9-16 Group inhibited
13-16 Group inhibited
All indoor run/stop selection switch
Use this to select the units to be run or stopped when the
ALL ON. or ALL OFF.O button has been pressed.
OFF : All indoor unit
ON: inhibited indoor unit
*All switches are OFF position at shipment.
12
OFF controller to the same address as the main
ON-OFF controller.
the main ON-OFF controller.
ON
1
2
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
ON
5
6
7
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
OFF OFF
ON
DIPSW1
1
2 3 4 5 6 7 8
Fig. 7
OI-744-12EG

Publicidad

Tabla de contenido
loading

Tabla de contenido