Troubleshooting - BAUKER DG5500E Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Maintenance in case the generator is stored for long periods.
If the generator is stored for a long time, it must be prepared as follows:
1- Remove the drain plug and pour the fuel tank.
2. Remove the air filter and drain the content in the crankshaft.
3- Reinstall the drain plug.
4- Refill with oil up to the maximum level on the dipstick.
5- Pull the start handle until there is no resistance.

Troubleshooting

Failure
Cause
The engine does not start.
1. The fuel tap is closed.
2. No fuel.
3. Insuff icient oil in the tank.
4. Air in the diesel fuel pipe.
5. The battery charge is too
low.
The engine runs irregularly.
1. Incorrect fuel.
2. Air in the diesel pipe.
The generator does not produce
• Short circuit.
current.
• Defective cable.
• Loose cable.
The generator shuts down while
1. The generator has run out of
running .
fuel.
2. Low oil level .
3. Failure in the generator.
The generator needs more
1. The load is too high .
power .
2. The air filter is dirty .
79
Solution
1. Make sure the fuel supply
tap and the switch are in the
"ON" position.
2. Make sure the tank has
sufficient fuel.
3. Oil refill.
4. Bleed the diesel fuel pipe .
5. Recharge the battery with an
adequate charger .
1. Make sure the right fuel is
used.
2. Bleed the diesel pipe.
1. If the indicator light does not
turn on, there is a failure that
you cannot fix by yourself.
If the indicator light turns on:
2. Push the overload fuse of
the used output.
3. Check the cables.
4. Check any short circ uits or
overloads.
1-Refill the fuel tank .
2- Refill with oil until the
appropriate level .
3-Contact the Authorized
Technical Serv ice.
1- Do not connect usage loads
greater than the generation
capacity . See the
ATS "AUTOMATIC TRANSFER SWITCH"
It is an electrical system that controls the automatic powering on and off of the
generator. This device switches from one supply source to another one. The
sources are the mains and the generator. When the mains power is interrupted,
the generator is powered on; and when the mains power is reestablished, the
generator is powered off. It is advisable to have an emergency circuit as a load
with power equal to or greater than that of the generator.
ATS control
Instruction manual
diesel generator
80

Hide quick links:

Publicidad

Tabla de contenido

Solución de problemas

loading

Productos relacionados para BAUKER DG5500E

Tabla de contenido