This adapter can also be used to test GFCI receptacles on 2-wire circuits. Connect the alligator
clip on the adapter to a ground, such as a metal water or gas pipe prior to testing the GFCI.
#61-176 Isolated Ground Adapter
This adapter allows the operator to verify that a receptacle is completely isolated from the system
ground that is bonded to other devices on the branch circuit. Test the ground impedance of the
receptacle and record the ohms value. (See the section on Line Impedance Testing for details on
obtaining the ground impedance value). Remove the SureTest and plug it into the isolated ground
adapter. Attach the alligator clip to the center receptacle screw or metal junction box, and re-
insert the SureTest into the receptacle and record the ohms value.
The isolated ground adapter creates a parallel pathway to ground, which results in a lower ground
impedance reading with the adapter versus with the receptacle with the isolated ground. If the two
readings are the same, then the receptacle does not have an isolated ground. If the reading taken
with the isolated ground adapter is lower, then the receptacle has an isolated ground.
Maintenance
Clean case with a damp cloth and mild detergent. Do not use abrasives or solvents.

Service and Replacement Parts:

This unit has no user-serviceable parts. To inquiry about service information, call Technical
Support at 877 201-9005 or visit our website at www.idealindustries.com.
Repair address is:
IDEAL INDUSTRIES, INC.
Attention: Repair Dept.
1000 Park Ave.
Sycamore, IL 60178