Low-Voltage PELV (Class 2: USA) Wiring Methods (choose one)
Control Interface Wiring:
Powered by GRAFIK Eye
Use Lutron Cable
GRX-CBL-346S
or equivalent
Control Interface Wiring:
Powered Directly
Data Link: (1) shielded, twisted
pair 18 AWG (1.0 mm
Use Lutron Cable
GRX-CBL-46L
PELV (Class 2: USA) Power wiring:
2: 24 V
Power
1: Common
(2) 18 AWG (1.0 mm
6 in (152 mm) maximum length
Wiring Notes
1. Strip 3/8 in (10 mm) of insulation from wires. Each
Data Link terminal will accept up to two 18 AWG
2
(1.0 mm
) wires.
2. Connect wiring as shown in the Wiring Diagrams. The
Status LED blinks once per second when properly
connected.
®
QS Control Unit
®
1 2 3 4 5 6 L N
Data Link:
4: MUX
3: MUX
One shielded, twisted
pair 18 AWG
2
(1.0 mm
) for data link
(terminals 3 and 4)
PELV (Class 2: USA) Power wiring:
2: Power
1: Common
Two 18 AWG (1.0 mm
2
) conductors
for Common (terminal 1) and
24 V
(terminal 2)
}
2
)
4: MUX
3: MUX
2
) pigtails,
Rear View of GRAFIK Eye QS Control Unit
Data
Link
To additional wallstations/control interfaces
D: Drain/Shield
Note: Do not connect drain/shield to
ground (earth) or wallstation/control
interfaces. Connect the bare drain
(2) 12 AWG
wires and cut off the outside shield.
2
(2.5 mm
)
Note: 12 AWG (2.5 mm
for Common (terminal 1) and
24 V
power (terminal 2) will not fit
in terminals; use 18 AWG (1.0 mm
pigtails, < 6 in (152 mm)
(2) 12 AWG
(2.5 mm
2
)
QSE-IO Control Interface Installation and Operation Instructions 3
2
) conductors
2
)