AC Shade Output:
1. Press and hold the open and close buttons on a QS shade
keypad or on a shade column of a GRAFIK Eye
for 3 seconds to enter programming mode. The LEDs on the
QSE-IO will turn off.
2. On the QSE-IO you wish to obey commands from that shade
keypad, tap the program button on the QSE-IO once to assign
shade Group 1 (LEDs 1-3 will blink), or twice to assign shade
Group 2 (LEDs 4-5 will blink).
Preset Adjust Mode
(Applies to 'Shade Input Preset' operating mode only.)
Three presets are available on QS shades. Shade default presets
are:
Preset 1: all assigned shades 75% open
Preset 2: all assigned shades 50% open
Preset 3: all assigned shades 25% open
To adjust these presets, follow these steps:
1. Press and hold the program button on the QSE-IO for 3 seconds
to enter programming mode. LEDs 1 and 5 will blink. Make sure
DIP switch 1 is up (On) and DIP switches 2 and 3 are down (Off).
2. Preset 1 will be selected. To advance through the presets, tap
the program button. To go to the previous preset, double-tap the
program button. LED 2, 3, or 4 will light to indicate which preset
is selected (1, 2, or 3).
3. When the desired preset is selected, press and hold the program
button for 2 seconds. All assigned QS shades will go to their
assigned value for the selected preset.
4. To select the shade you want to change, tap the program button
to advance through the assigned shades. The selected shade will
wiggle up and down.
5. When the desired shade is wiggling, set DIP switch 2 up (On).
The shade will stop wiggling.
6. To move the selected QS shade to the desired position for this
preset, either set DIP switch 3 up (On) and use the program
button to raise the QS shade, or set DIP switch 3 down (Off) to
and use the program button to lower the QS shade.
Preset Adjust Mode DIP Switch Settings Summary
Position
1
Up
Preset adjust mode
Down
Shade assign mode
Special Configuration Functionality
Sequence 5-16: Causes assigned control units to continuously
cycle through scenes 5-16 using the programmed fade times for
each scene.
Zone Lockout: Causes assigned control units to not update their
currently active scene when individual zone raise/lower buttons
are pressed, no matter what save mode is selected.
®
3. To unassign shade Group 1, tap the program button once when
QS control unit
LEDs 1-3 are blinking; the LEDs will stop blinking. To unassign
®
shade Group 2, double-tap the program button once when LEDs
4-5 are blinking; the LEDs will stop blinking.
4. Press and hold the open and close buttons on the shade keypad
for 3 seconds to exit programming mode.
7. To move to another shade, set DIP switch 2 down (Off). Repeat
steps 4 through 6 until all shades are set as desired for this
preset.
8. With DIP switch 2 down (Off), press and hold the program button
on the QSE-IO for 3 seconds to save this preset. Return to step 2
to adjust additional presets.
9. Press and hold the program button for 10 seconds to exit
programming mode.
Note: At any point while DIP switch 2 is down (Off), press and
hold the program button for 10 seconds to exit program mode
without saving any presets.
DIP Switch Number
2
Individual shade is selected
for adjusting preset
Select shade to adjust
when in preset adjust mode
Scene Lockout: Disables all buttons on assigned control units.
Panic Mode: Causes all assigned control units to go to Scene
16, and disables buttons, wallstations, and IR control.
Timeclock Disable: Disables the timeclock on all assigned control
units.
QSE-IO Control Interface Installation and Operation Instructions 7
3
Press program button to raise shade
(DIP switches 1 and 2 must be up)
Press program button to lower shade
(DIP switches 1 and 2 must be up)