INSTALLATION INSTRUCTIONS
E-WRC Series
CAUTIONS
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety
precautions should always be followed including the
READ AND FOLLOW ALL
SAFETY INSTRUCTIONS
1.
DANGER- Risk of shock- Disconnect power before
installation.
DANGER – Risque de choc – Couper l'alimentation
avant l'installation.
2.
This Product Must Be Installed In Accordance With The
Applicable Installation Code By A Person Familiar With
The Construction And Operation Of The Product And The
Hazards Involved.
Ce Produit Doit Être Installé Selon Le Code D'installation
Pertinent, Par Une Personne Qui Connaît Bien Le
Produit Et Son Fonctionnement Ainsi Que Les Risques
Inhérents.
3.
Suitable for Wet Locations.
Adspte pour les Endroits Mouiles.
4.
WALL MOUNT ONLY.
INSTALLATION MURALE SEULEMENT.
5.
Suitable for maximum ambient of 45C.
Peut etre utilise pour maximum 45C temperature
ambiante.
6.
Min. 90°C supply conductors.
Les fils d'alimentation 90°C min.
SAVE THESE INSTRUCTIONS
FOR FUTURE REFERENCE
MOUNTING OVER RECESSED JUNCTION BOX
NOTE: Knockouts are provided for mounting over 3" octagonal or 4"
octagonal junction boxes.
1. Remove lens assembly by loosening screws on side of frame.
Swing lens assembly open, and lift lens assembly upward to
remove from housing. Set lens assembly aside for later use.
following:
www.e-conolight.com
LPN00841X0001A0_A
Document:
Created By:
TMT
2. Drill out appropriate knockouts in back box for attachment to junction
box. Also, if present, remove threaded plug in center of back wall of
box for wiring access.
NOTE: Fixture should not be exclusively supported by junction
box. Drill additional knockouts toward corners of fixture to provide
additional support. Do NOT drill within 1/4" (64 mm) from edges of
fixture.
3. Pull supply leads from junction box through wall of back box. Attach
back box to mounting surface using hardware (supplied by others)
appropriate for mounting surface.
NOTE: A high grade caulking material, such as silicone rubber,
MUST be used around perimeter of back gasket and at support
locations in the four corners of the fixture to prevent water leakage
into fixture or junction box.
4. Set dip switch inside lens assembly for desired color temperate
(CCT). Default setting is 4000k. Switch can also be adjusted for 3000k
or 5000k. See Figure 1.
5. Replace the lens assembly on the hinges.
6. Make wiring connections per the Electrical Connections section.
7. Close lens and re-tighten screws that were loosened in Step 1.
WALL MOUNTED WITH CONDUIT FEED
1. Remove lens assembly by loosening screws on side of frame. Swing
lens assembly open, and lift lens assembly upward to remove from
housing. Set lens assembly aside for later use.
2. Drill out junction box knockouts in center of back box to allow for
attachment of back box to mounting surface.
3. Attach back box to mounting surface using hardware (supplied by
others) appropriate for mounting surface.
NOTE: A high grade caulking material, such as silicone rubber,
MUST be used around perimeter of back gasket to prevent water
leakage into fixture or junction box.
4. Remove appropriate threaded plugs on sides of fixture and route
electrical conduit to the holes desired. Feed the supply leads through
the conduit and into the back box.
NOTE: Use of teflon tape on the conduit threads will ensure a
watertight seal.
5. Set dip switch inside lens assembly for desired color temperate
(CCT). Default setting is 4000k. Switch can also be adjusted for 3000k
or 5000k. See Figure 1.
6. Replace the lens assembly on the hinges.
7. Make wiring connections per the Electrical Connections section.
8. Close lens and re-tighten screws that were loosened in Step 1.
FIGURE 1
DIP Switch
CCT Sticker
3000K
4000K
5000K
|
888.243.9445
|
FAX: 262.504.5409
09-25-2020
Date
ECO#
012077