General
The RS photo-cell control kit is designed to automatically switch lighting
(or other) loads on and off depending on the ambient lighting levels.
The unit has factory set lighting levels and is omni-directional i.e., it
does need north orientation. Additionally it has a built-in time delay to
stop unwanted nuisance switching by car headlights, passing clouds
etc.
The kit comprises of the following:
1 x Photo-electric cell
1 x Rotaloc socket
1 x Neoprene gasket
1 x Dust cap
4 x Posidriv® socket fixing screws
1 x Fixing bracket
1 x Rubber grommet
3 x No. 8 x 11⁄4" wood screws
3 x No. 8 wall fixing plugs
Installation
Before installation choose a suitable location for the controller, avoid
positions where light from other sources can influence the switching
also locations which may fall into shadow in the morning and evening
i.e. eaves of a building.
As a general rule the controller should also be mounted in a position
that makes it inaccessible to unauthorised personnel.
To install the photo-cell (refer to Figure 2).
1. Drill mounting holes for the fixing bracket, using the bracket as a
template.
Fix securely in position using a no. 8 masonry drill and the wall plugs
and screws supplied.
2. Puncture the rubber grommet located at the base of the mounting
bracket and install appropriate cable or alternatively remove
grommet and connect 20mm conduit.
The controller may be used to directly switch lighting loads up to its
maximum rating (see Technical specification) or alternatively it may
be used in conjunction with a contactor to supply a multi-load
installation (refer to Figures 2 and 3 for typical wiring diagrams).
3. Before connecting cable to socket ensure that the neoprene gasket
is located between the bracket and the socket.
4. Connect cable as per Figure 4.
Li = Line = Live (phase) supply
N = Neutral = Neutral
LO = Load = Out-going switched live
Neutral connection can be used as looped connection to neutral
terminal on load if required (see Figures 2 and 3).
5. Fix socket to bracket using the 4 posidriv® screws provided.
6. Plug the photo-cell unit into the socket by pushing down firmly and
then twisting clockwise to its full extent.
The photo-cell unit will only fit the socket in one position. Ensure that
the large lug on the cell locates in the large slot of the socket.
7. Once the kit is fully assembled the unit is now ready for connection
to the supply. Check the connections on the load being supplied
before switching on.
When supply is first switched on, unit will be alive and the load will be
switched on. After 5 to 30 seconds the unit should switch off.
To test the unit cover the photo-cell completely the load will switch on.
Note: That the same time delay will exist on both switching on and off.
Remove the cover and wait for the unit to switch off.
Important: Supply to the photo-cell must be maintained at all times.
The supply to the Li terminal will still be alive when the
load is switched off.
Testing
RS Stock No.
Insulation testing by suitable instrument can be carried out on circuits
including photo-cells, but not continuity tests as the high voltage used
472-1486
may seriously damage the cell.

Technical specification

Type of control: __________________________________Electronic
Supply voltage: ______________________________240V
Rating: ______________5A inductive: tungsten filament, fluorescent
Switch on level: ____________________________________70 lux
Switch off level: ____________________________________105 lux
Operation: ________________________________________All night
RS Components shall not be liable for any liability or loss of any nature (howsoever
caused and whether or not due to RS Components' negligence) which may result
from the use of any information provided in RS technical literature.
Allgemein
Die RS Fotozellensteuerung wurde entwickelt, um automatisch
Lichtschaltkreise (oder andere) in Abhängigkeit von der Stärke des
Umgebungslichts ein- und auszuschalten.
Diese Einheit ist ungerichtet (eine Nordausrichtung ist nicht
erforderlich). Die einzelnen Lichtstärkepegel sind werkseitig eingestellt.
Sie verfügt außerdem über eine eingebaute Zeitverzögerung, um
Fehlschaltungen durch die Scheinwerfer eines Autos, durch
vorüberziehende Wolken usw. zu vermeiden.
Zum Lieferumfang gehören:
1 Fotozelle
1 Rotaloc-Buchse
1 Neopren-Dichtung
1 Staubkappe
4 Schrauben zur Befestigung der Posidriv® Buchse
1 Halterung
1 Durchführungstülle aus Gummi
3 Holzschrauben 8 x 11/ 4"
3 Dübel Nr. 8
Montage
Wählen Sie vor der Montage den geeigneten Platz aus. Vermeiden Sie
Stellen, an denen eintreffendes Licht von anderen Quellen das
einwandfreie Schalten beeinflußen kann und solche Stellen, die
morgens und abends im Schatten liegen, d.h. Vordächer.
Die Steuerung sollte im allgemeinen so montiert sein, daß sie für
unbefugte Personen nicht zugänglich ist.
Montage der Fotozelle (siehe Abbildung 2).
1. Bohren Sie die Löcher für die Halterung. Benutzen Sie die Halterung
als Schablone.
Benutzen Sie einen Maurerbohrer Nr. 8, setzen Sie die Dübel ein,
und befestigen Sie die mitgelieferten Schrauben.
2. Durchstechen Sie die Gummitülle im Sockel der Halterung, und
ziehen Sie das entsprechende Kabel ein. Sie können die Tülle auch
entfernen und ein 20mm Kabel anschließen.
Mit dem Steuergerät können Sie Lichtlasten bis zu ihrer maximalen
Leistung direkt schalten (siehe "Technische Daten"). Sie können es
auch
Mehrlastanschluß benutzen (siehe die Abbildungen 2 und 3 der
typischen Verdrahtungspläne).
3. Bevor Sie das Kabel an die Buchse anschließen, sollten Sie
sicherstellen, daß die Neoprendichtung richtig zwischen Halterung
und Buchse sitzt.
and low pressure sodium lamp 2 x 250W
high pressure sodium and metal halide lamps
in
Verbindung
mit
einem
V8493
50Hz
RS Best-Nr.
472-1486
Schaltschütz
für
einen
3