Compatibilidad Electromagnética; Aislamiento - LEGRAND EMDX³ S96 Manual De Instrucciones

Tabla de contenido

Publicidad

E
PRECISIÓN
Precisión en la energía activa :
Precisión en la energía reactiva :
MARCADO CE
The 146 68 product complies with :
The requirements of the European directive on electromagnetic compatibility (EMC) no. 89/336/CEE dated 3 May 1989,
modi ed by directive no. 92/31/CEE dated 28 April 1992 and by directive no. 93/68/CEE dated 22 July 1993.
Low voltage directive no. 73/23/CEE dated 19 February 1973, modi ed by directive no. 93/68/CEE dated 22 July
1993, modi ed by directive no. 2006/95/CE.
COMPATIBILIDAD ELECTROMAGNÉTICA
Immunity to electrostatic discharges:
Immunity to radiated radio-frequency elds:
Immunity to electrical fast transients/bursts:
Immunity to surge immunity:
Immunity to conducted disturbances:
Immunity to power frequency magnetic elds:
Conducted and radiated emissions:
Immunity to voltage dips and short interruptions:
CLIMAT
Operating-temperature range:
Storage temperature range:
Humidity:
Salt mist:
CARACTERÍSTICAS MECÁNICAS
Vibration from 10 to 50 Hz :

AISLAMIENTO

Installation category:
Degree of pollution:
Rated impulse withstand voltage:
Front face:
Electric safety:
CARACTERÌSTICAS DEL PMD
Tipo de característica
Función (eventual) de evaluación de la cali-
dad de la alimentación
Clasi cación de los PMD
Temperatura
Humedad + Altitud
Clase de rendimiento de funcionamiento
de la potencia activa o de la energía activa
(si la función se encuentra disponible)
CONFORMIDAD CON IEC 61557-12 Edition 1 (08/2007)
Ejemplo de valores
característicos posibles
IEC 62053-22 clase 0,5S
IEC 62053-23 clase 2
IEC 61000-4-2 - Level III
IEC 61000-4-3 - Level III
IEC 61000-4-4 - Level III
IEC 61000-4-5 - Level III
IEC 61000-4-6 - Level III
IEC 61000-4-8 - Level III
CISPR11 - Clase A
IEC 61000-4-11
IEC 60068-2-1/IEC 60068-2-2
-10 °C to +55 °C
IEC 60068-2-1/IEC 60068-2-2
-20 °C to +85 °C
IEC 60068-2-30 - 95 %
IEC 60068-2-52 - 2,5 % NaCl
IEC 60068-2-6 - 2 g
III (480 VAC ph /ph)
2
IEC 60947-1 - V imp: 4 kV
Clase II
IEC 61010-1
-
SD
K55
-
0,5
CARACTÉRISTIQUES TECHNIQUES
Otras características
-
-
-
-
-
146 68 - Ref.: N292510/00