Hollow
Metal
or
Wood Door
3/8" Glazing Space
3/16", 1/4"
or 5/16" GLASS
1/2"
1"
Hollow
Metal
or
Wood Door
3/32"
1 3/4"
UL10C Positive Pressure rated fire doors using Pyran
PVC foam glazing tape like NGP L-GT-116, L-GT-118, L-GT-132 or L-GT-316.
7.20
Fire Door Glass
Light Frame
National Guard Products Inc.
L-CVFM-SS
for 1-3/4" Door,
3/16", 1/4", or 5/16" Glass
1. Cut out door in accordance with door manufacturers listing procedure. Steel
fire-rated doors do NOT require an opening reinforcing channel or reinforc-
ing clips.
2. Install glass & glazing material (sold separately), into lite kit.
3. Position outer frame in door cut out.
4. Position inner frame and insert and start all screws before fully tightening.
5. Tighten screws using a criss cross pattern. Use caution when using power
screw driving equipment to avoid stripping the material.
For Fire Rated Doors, using 1/4" fire rated wired glass:
20 & 45 minute = 1,296 sq. inches max visible glass, 54" max height, 54" max width.
60 & 90 minute = 100 sq. inches max visible glass, 33" max height, 10" max width.
Sizes exceeding those shown above may be achieved using Pyran
F, Protect3™ or TEMP20™. Maximum size is determined by the glass listing (in
doors) and door manufacturers listing.
UL10C Positive Pressure rated fire doors using 1/4" fire-rated wired glass:
20 min requires closed cell PVC foam glazing tape like NGP L-GT-116,
L-GT-118, L-GT-132 or L-GT-316.
45, 60 or 90 min requires NGP 9800C or 3M GIS intumescent glazing tape.
Platinum F, Protect3™ or TEMP20™ requires closed cell
®
1-800-647-7874
Installation Instructions
Platinum
®

Publicidad

loading

Resumen de contenidos para NGP L-CVFM-SS

  • Página 1 Wood Door L-GT-118, L-GT-132 or L-GT-316. 3/32" 1 3/4" 45, 60 or 90 min requires NGP 9800C or 3M GIS intumescent glazing tape. UL10C Positive Pressure rated fire doors using Pyran Platinum F, Protect3™ or TEMP20™ requires closed cell ®...
  • Página 2 Puertas certificadas cortafuego de Presión Positiva que cumplen con lo establecido en UL10C y que usan vidrio armado certificado cortafuegos de 1/4": 20 minutos requieren cinta espuma adhesiva PVC de celda cerrada como NGP L-GT-116, L-GT-118, L-GT-132 ó L-GT-316. 45, 60 ó 90 minutos requieren NGP 9800C ó sello intumescente 3M GIS.