Transponder card reader for installation outside rooms, KNX stan-
dard, 2 NO 4 A 24 V~ relay outputs, 2 inputs, power supply 12-24 V~
50-60 Hz and 12-24 V d.c. (SELV) - 3 modules.
The device, with transponder cards, enables controlling entry to the rooms where it
is installed externally. The transponder reader is provided with two relays to control
the door lock, to control a courtesy light, or for other uses; the device is moreover
provided with two inputs for connecting electrical equipment of the ON / OFF type
(for example to control the switch for door opening and closing, a magnetic contact
for signalling windows open or closed, ceiling pull alarm, etc.).
On the front of the reader there are four LEDs each of which associated with an
icon for signalling the following states:
- Access (entry allowed or entry denied);
- Guest status (room occupied or do not disturb);
- Call status (rescue request with bathroom ceiling pull-cord, room service call, etc.);
- Services status (make up room, etc.).
The transponder reader is able to dialogue with other KNX components via the
specific interface.
CHARACTERISTICS.
• Supply voltage:
- BUS: 29 V SELV
- 12-24 V ± 20% SELV
• Consumption:
- on the bus: 10 mA
- on the power supply (at 12-24 V ): 130 mA max
• Terminals:
- TP bus
- power supply (12-24 V )
- digital inputs for 2 NO or NC contacts (with no potential, SELV)
- outputs for 2 NO relays (24 V~ SELV 4 A cos 1; 24 V~ SELV 2 A cos 0.6)
• Frequency range: 13,553-13,567 MHz
• RF transmission power: < 60 dBμA/m
• Operating temperature: -5 °C - +45 °C (inside)
• This device contains only SELV circuits that must be kept separate from circuits
with dangerous voltage
OPERATION.
The configuration of the reader, physical address and parameters (NO or NC contact
inputs, normal or timed relay outputs, etc.) is done with the ETS software.
If the transponder reader is loaded with an incorrect ETS application, both the red
LED on the back of the device and the front LEDs 2, 3 and 4 will blink ("device
type" error). To restore the desired configuration, load the device with the correct
ETS application.
The card is read by putting it in front of the reader that in sequence checks:
- "system code" (whether consistent);
- "date" field (if enabled, it checks whether the validity has expired);
- "password" (checks all the codes associated with it and enabled, such as guest
code, service code, timeframes).
IMPORTANT: The transponder card readers should be fed separately from all
other loads (electric locks, lamps, contactors, etc.) using a 16887 transformer
dedicated to them whose outputs will be used only for these two devices.
Important: The length of the cable for connecting the inputs must not exceed
30 m.
NB: In the phase of installation provide for cable connection lengths that allow
extracting the device from the flush mounting box so as to be able to access the
configuration button.
For the 12-24 V
power supply use 12/24 V d.c. power supplies or transformers
with secondary winding having extra low voltage (SELV) for continuous service; do
not use the voltage transformers for doorbells.
INSTALLATION RULES.
Installation should be carried out by qualified staff in compliance with the current
regulations regarding the installation of electrical equipment in the country where
the products are installed.
CONFORMITY.
RED directive.
Standards EN 50491, EN 60669-2-5, EN 300 330, EN 62479, EN 301 489-3.
49400222D0 02 2001
Idea
Plana
16927
14457
FRONT VIEW.
1
2
3
4
LED STATUS.
• LED 1:
- steady green: signalling "Entry allowed" (the LED remains illuminated for approxi-
mately 3 s).
- blinking green: signalling if the timeframe is not valid (the LED blinks for approxi-
mately 3 s).
- steady red: signalling "Entry denied" (the LED remains illuminated for approxima-
tely 3 s).
- blinking red: signalling if the expiry date is not valid.
- steady amber: signalling if the system coding is not valid.
- blinking amber: signalling if the day of the week is not valid.
- blinking red/green: synchronize the device's internal clock.
• LED 2:
- red: signalling "Do Not Disturb".
- blinking red: signalling "Room occupied".
: amber - signalling "Room service call."
• LED 3
• LED 4: green - signalling "Make up room."
Note.
The meaning taken on by the LEDs depends on the subjects of communication (therefore the functions)
that are configured in the reader with the ETS software. For all the applications in which the device is
configured with different functions and LED indications to the standard ones, the customer can ask
Vimar to customize the symbols on the front of the reader with a laser.
REAR VIEW.
Configuration BUTTON
C NO
Relay 1
C
NO
Relay 2
Power supply
12-24 V
• Configuration BUTTON: button for switching between normal mode or programming
mode or detecting the physical address.
• LED off: "normal operation" indicator.
• Red LED: "addressing mode" indicator (the LED goes out automatically after program-
ming the physical address).
Vimar SpA declares that the radio equipment complies with Directive 2014/53/EU.
The full text of the EU declaration of conformity is on the product sheet available at
the following Internet address: www.vimar.com.
REACH (EU) Regulation no. 1907/2006 – Art.33. The product may contain traces
of lead.
WEEE - Information for users
If the crossed-out bin symbol appears on the equipment or packaging, this means the product must not
be included with other general waste at the end of its working life. The user must take the worn product
to a sorted waste center, or return it to the retailer when purchasing a new one. Products for disposal can
be consigned free of charge (without any new purchase obligation) to retailers with a sales area of at least
400 m
2
, if they measure less than 25 cm. An efficient sorted waste collection for the environmentally friendly
disposal of the used device, or its subsequent recycling, helps avoid the potential negative effects on the
environment and people's health, and encourages the re-use and/or recycling of the construction materials.
LED
IN1
BUS line
IN2
Common
~
inputs
1 and 2
Viale Vicenza, 14
36063 Marostica VI - Italy
www.vimar.com

Publicidad

loading

Este manual también es adecuado para:

Arké 19457Idea 16927Plana 14457Plana 14457.slIdea 16927.bArké 19457.b ... Mostrar todo