To Install The Outdoor Unit; To Provide Drainage - Daikin Altherma 3R Manual Del Usuario

Ocultar thumbs Ver también para Altherma 3R:
Tabla de contenido

Publicidad

4 Unit installation
INFORMATION
The recommended height of the upper protruding part of
the bolts is 20 mm.
NOTICE
Fix the outdoor unit to the foundation bolts using nuts with
resin washers (a). If the coating on the fastening area is
stripped off, the metal can rust easily.
a
4.2.2

To install the outdoor unit

CAUTION
To avoid injury, do NOT touch the air inlet or aluminium
fins of the unit.
1 Put the sling (delivered as accessory) through the unit's left
feet.
2 Carry the unit using the sling (left) and the unit's handles (right),
and put it onto the installation structure.
±101
kg
3 Remove the sling, and dispose of it.
4 Fix the unit to the installation structure.
Installation manual
10
4.2.3

To provide drainage

Make sure that condensation water can be evacuated properly.
INFORMATION
If necessary, you can use a drain pan (field supply) to
prevent drain water from dripping.
NOTICE
If the unit CANNOT be installed fully level, always make
sure that the inclination is towards the backside of the unit.
This is required to guarantee proper drainage.
NOTICE
If drain holes of the outdoor unit are covered by a mounting
base or by floor surface, raise the unit to provide a free
space of more than 150 mm under the outdoor unit.
Drain holes (dimensions in mm)
A
171
758
B
43
48
107
288
451
613
776
A
Discharge side
B
Distance between anchor points
C
Bottom frame
D
Drain holes
E
Knockout hole for snow
4× M12
206
C
D
=
E
ERLA11~16DAV3+W1
Daikin Altherma 3 R
4P643598-1 – 2021.09

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Erla11dav3Erla14dav3Erla16dav3Erla11daw1Erla14daw1Erla16daw1

Tabla de contenido