  • Página 1 Installation manual Daikin Altherma 3 R Installation manual English Daikin Altherma 3 R ERGA04DAV37...
  • Página 2 2P491692-4D...
  • Página 3 2P491692-4D...
  • Página 4: Tabla De Contenido

    Opening the units ..............Daikin website (publicly accessible). 4.1.1 To open the outdoor unit..........▪ The full set of latest technical data is available on the Daikin Mounting the outdoor unit............Business Portal (authentication required). 4.2.1 To provide the installation structure ......
  • Página 5: To Remove The Accessories From The Outdoor Unit

    Mind the following spacing guidelines: >250 >350 Protect the outdoor unit against direct snowfall and take care that the outdoor unit is NEVER snowed up. >250 >250 (mm) (mm) Air outlet Air inlet ERGA04DAV37 Installation manual Daikin Altherma 3 R 4P618926-1 – 2020.03...
  • Página 6: Installation

    100  mm above the maximum expected level of snow. INFORMATION The maximum height of the upper protruding part of the 0 mm bolts is 15 mm. Installation manual ERGA04DAV37 Daikin Altherma 3 R 4P618926-1 – 2020.03...
  • Página 7: To Install The Outdoor Unit

    ▪ (3) Fix the unit. 2× Air outlet NOTICE Properly align the unit. Make sure the backside of the unit does NOT protrude. (mm) Maximum snowfall height EKFT008D option kit Anti-vibration rubber (field supply) ERGA04DAV37 Installation manual Daikin Altherma 3 R 4P618926-1 – 2020.03...
  • Página 8: To Provide Drainage

    3 Insert a rubber sheet between the cables and the outdoor unit Drain hole insulation to prevent the cables from scratching the paint (field supply). 4 Attach the ends of the cables. 5 Tighten the cables. Installation manual ERGA04DAV37 Daikin Altherma 3 R 4P618926-1 – 2020.03...
  • Página 9: Connecting The Refrigerant Piping

    200  kPa (2  bar). It is recommended to pressurize to 3000 kPa (30 bar) in order to detect small leaks. 2 Check for leaks by applying the bubble test solution to all connections. 3 Discharge all nitrogen gas. ERGA04DAV37 Installation manual Daikin Altherma 3 R 4P618926-1 – 2020.03...
  • Página 10: To Charge Additional Refrigerant

    2 Fix the label on the inside of the outdoor unit near the gas and liquid stop valves. 2 Connect the interconnection cable and power supply as follows. Ensure stress relief by using the wire clamp. Installation manual ERGA04DAV37 Daikin Altherma 3 R 4P618926-1 – 2020.03...
  • Página 11: Finishing The Outdoor Unit Installation

    4 Optional: Attach the wire clamp (accessory) to the screw of the refrigerant piping cover, and fix the cables to it with a cable tie. 1× 1× 5 Connect an earth leakage circuit breaker and fuse to the power supply line. ERGA04DAV37 Installation manual Daikin Altherma 3 R 4P618926-1 – 2020.03...
  • Página 12: Technical Data

    6 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). Piping diagram: Outdoor unit 7.0 CuT...
  • Página 13: Wiring Diagram: Outdoor Unit

    Printed circuit board (main) PCB2 Printed circuit board (service) Switching power supply Thermal protector Q1DI # Earth leakage circuit breaker Insulated gate bipolar transistor (IGBT) Thermistor (air) Thermistor (heat exchanger) Thermistor (discharge) ERGA04DAV37 Installation manual Daikin Altherma 3 R 4P618926-1 – 2020.03...