P5: Maximum fan speed voltage: value in the range between 6 and 10V. (Default value:
9.5V);
P6: UV-C lamp control: value in the range between 0 and 4. (Default value: 0).
Meaning of the parameter values:
0: lamp permanently off
1: lamp on (operation according to time, par. 8 and 9). Activation only when the device is
2: lamp on (operation according to par. 8 and 9). Activation only when the device is
3: lamp on (operation according to time, par. 8 and 9). Activation independent of device
4: lamp on (operation according to time, par. 8 and 9). Activation independent of device
P7: Fan speed with lamp on: value in the range between 20% and 100%. (Default value:
30%)
P8: Switch-on time of the UV-C lamp: value in the range between 00:00 and 23:00.
(Default value: 19:00)
P9: Switch-off time of the UV-C lamp: value in the range between 00:00 and 23:00.
(Default value: 06:00)
P10: hours of UV-C lamp operation before "replace lamp" signal. The possible values are
"OFF" and a value in the range between 1 and 20000 h. (Default value: 12000 h);
P11: Communication address: value in the range between 1 and 240. (Default value: 1)
32
switched on. Fan speed: manual setting
switched on. Fan speed: par. 7
on/off status. Fan speed: default value (70%) (record 3)
on/off status. Fan speed: par. 7