Vortice Reg Depuro Plus Manual De Instrucciones página 38

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

ENGLISH
Record 5: Set fan speed period 2 (time programming) [read / write].
The value that is sent is the speed value (0% to 100%) in 16-bit binary.
Default value: 30 [30%: Fan on].
Record 6: Setpoint fan speed reduced period (time programming) [read / write].
The value that is sent is the speed value (0% to 100%) in 16-bit binary.
Default value: 0 [0%: Fan off].
Record 7: Minimum fan speed voltage [read / write].
The value that is sent is the voltage value (0.0V to 5.0V) multiplied by 10 in 16-bit binary.
Default value: 20 [2,0V].
Record 8: Maximum fan speed voltage [read / write].
The value that is sent is the voltage value (6.0V to 10.0V) multiplied by 10 in 16-bit binary.
Default value: 95 [9,5V].
Record 9: F7 filter operating time Hours [read / write]. Only allowed write value: 0 (reset).
The value that is sent is the value of the hours (0h to 65000h. The value of 65000h does not overflow) in 16-bit
binary. Default value: 0 [0h].
Record 10: F7 filter operating time Minutes [read / write]. Only allowed write value: 0 (reset).
The value that is sent is the value of the hours (0min to 59min) in 16-bit binary.
Default value: 0 [0min].
Note: The operating time (Records 9 and 10) only increases if the fan is operating (Record 57 ≠ 0),
Record 11: F7 filter operating hours for dirty filter indication (timer) [read / write].
The value that is sent is the value of the hours (disabled function: 0, 1h to 9000h) in 16-bit binary.
Default value: 8000 [function enabled, and F7 dirty filter indication with operating hours ≥ 8000h].
= 0: Function disabled.
> 0: Function enabled.
Record 12: pre filter operating time Hours [read / write]. Only allowed write value: 0 (reset).
The value that is sent is the value of the hours (0h to 65000h. The value of 65000h does not overflow) in 16-bit
binary.
Default value: 0 [0h].
Record 13: pre filter operating time Minutes [read / write]. Only allowed write value: 0 (reset).
The value that is sent is the value of the hours (0min to 59min) in 16-bit binary.
Default value: 0 [0min].
Note: The operating time (Records 9 and 10) only increases if the fan is operating (Record 57 ≠ 0),
Record 14: pre filter operating hours for dirty filter indication (timer) [read / write].
The value that is sent is the value of the hours (disabled function: 0, 1h to 9000h) in 16-bit binary.
Default value: 4000 [function enabled, and pre filter dirty filter indication with operating hours ≥ 4000h].
= 0: Function disabled.
> 0: Function enabled.
Record 15: H14 filter operating time Hours [read / write]. Only allowed write value: 0 (reset).
The value that is sent is the value of the hours (0h to 65000h. The value of 65000h does not overflow) in 16-bit
binary.
Default value: 0 [0h].
Record 16: H14 filter operating time Minutes [read / write]. Only allowed write value: 0 (reset).
The value that is sent is the value of the hours (0min to 59min) in 16-bit binary.
Default value: 0 [0min].
Note: The operating time (Records 12 and 13) only increases if the fan is operating (Record 51 ≠ 0),
Record 17: Hours of operation of H14 filter for indication of dirty filter (timer) [read / write].
The value that is sent is the value of the hours (function disabled: 0, 1h to 9000h) in 16-bit binary.
Default value: 7305 [function enabled, and indication of dirty filter H14 with operating hours ≥ 7305h].
= 0: Function disabled.
> 0: Function enabled.
Record 18: PHOTOCATALYSIS-UVC module control [read / write].
High byte: Enable / disable PHOTOCATALYSIS-UVC module.
0: EVO module with PHOTOCATALYSIS-UVC module disabled.
The EVO MODEL with PHOTOCATALYSIS-UVC module remains permanently off.
1: EVO module with PHOTOCATALYSIS-UVC module enabled
The EVO MODEL with PHOTOCATALYSIS-UVC module is activated only if fan on (Record 57 ≠ 0) Fan speed
= Record 3.
Operation of the PHOTOCATALYSIS-UVC module according to schedule (Record 19).
2: EVO MODEL with PHOTOCATALYSIS-UVC module enabled
The EVO MODEL with PHOTOCATALYSIS-UVC module is activated only if fan on (Record 57 ≠ 0) Fan speed
= Record 18 (low byte).
3: EVO MODEL with PHOTOCATALYSIS-UVC module enabled
The EVO MODEL with PHOTOCATALYSIS-UVC module is activated regardless of the fan status. Fan speed
=Registration 3.
38

Publicidad

Tabla de contenido
loading

Tabla de contenido