Preparation

3.1

Preparing the installation site

WARNING
The appliance shall be stored in a room without
continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric
heater).
3.1.1
Installation site requirements of the

outdoor unit

Mind the following spacing guidelines:
b
>100
a
>50
b
>150
a
>50
(mm)
a
Air outlet
b
Air inlet
NOTICE
The height of the wall on the outlet side of the outdoor unit
MUST be ≤1200 mm.
It is recommended to install a baffle plate when the air outlet is
exposed to wind.
It is recommended to install the outdoor unit with the air inlet facing
the wall and NOT directly exposed to the wind.
b
a
Baffle plate
b
Prevailing wind direction
c
Air outlet
Do NOT install the unit in sound sensitive areas (e.g. near a
bedroom), so that the operation noise will cause no trouble.
Note: If the sound is measured under actual installation conditions,
the measured value might be higher than the sound pressure level
mentioned in "Sound spectrum" in the data book due to
environmental noise and sound reflections.
RXTM30+40N2V1B + RXTP25+35N2V1B9 + ARXTP25+35N2V1B +
RXTA30N2V1B
R32 split series
3P482320-10M – 2019.04
a
>150
b
>50
b
>100
a
a
>100
b
b
a
Do NOT install the unit in sound sensitive areas (e.g. near a
bedroom), so that the operation noise will cause no trouble.
INFORMATION
The sound pressure level is less than 70 dBA.
3.1.2
Additional installation site requirements
of the outdoor unit in cold climates
Protect the outdoor unit against direct snowfall and take care that the
outdoor unit is NEVER snowed up.
c
a
Snow cover or shed
b
Pedestal
c
Prevailing wind direction
d
Air outlet
In any case, provide at least 300  mm of free space below the unit.
Additionally, make sure the unit is positioned at least 100 mm above
the maximum expected level of snow. See
outdoor unit" on page 7
for more details.
In heavy snowfall areas it is very important to select an installation
site where the snow will NOT affect the unit. If lateral snowfall is
possible, make sure that the heat exchanger coil is NOT affected by
the snow. If necessary, install a snow cover or shed and a pedestal.
3.1.3
Refrigerant piping length and height
difference
What?
Maximum allowable pipe length
Minimum allowable pipe length
Maximum allowable height difference
4

Installation

WARNING
Installation shall be done by an installer, the choice of
materials and installation shall comply with the applicable
legislation. In Europe, EN378 is the applicable standard.
4.1

Mounting the outdoor unit

4.1.1

To provide the installation structure

Use a vibration-proof rubber (field supply) in cases where vibrations
may be transmitted to the building.
3 Preparation
a
c
b
"4.1  Mounting the
Distance
20 m
1.5 m
15 m
Installation manual
7