Supplies Required; Secure Base To Floor; Assemble Components; Connect Water Supply - Bradley S19-310 Instrucciones De Instalación

Combinación de ducha de aspersión y lavaojos
Ocultar thumbs Ver también para S19-310:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

S19-310

Supplies Required

• (3) 3/8" floor anchors and bolts
• Teflon tape and pipe sealant
• Piping to 1¼" NPT water supply inlet and 1¼"
NPT drain outlet on unit
• Adequate supply pipe supports
• Minimum 4" (102mm) drain to accommodate 30
gallons (115 liters) per minute discharge for shower
waste
• OPTIONAL: sign-mounting hardware
Local codes may require the installation of a
backflow prevention valve to complete proper
installation. Backflow prevention valves are not
included with the fixture and may be supplied
by the contractor or purchased from Bradley
Corporation.

Secure base to floor

1. Install three suitable anchors (supplied by
installer) for 3⁄8" bolts in the floor.
2. Bolt the base to the floor anchors using 3⁄8"
bolts (supplied by installer).

Assemble components

1. Assemble the remaining unit components as
shown on page 4. For ease of installation,
disassemble the union (#18) prior to assembly.
2. Apply pipe sealant (by installer) to all male-
threaded pipe joints.
3. Use the rubber grip pad provided or a strap
wrench around pipes when tightening to prevent
marring the Bradtect® protective, safety yellow
coating. Place the grip pad on the pipe, then put
the wrench over the grip pad and turn the pipe
with the wrench.
4. Bottom edge of the showerhead should be 86"
(2180mm) from floor.

Connect water supply

NOTICE! Do not rely on Bradley's Combination Unit
to support supply piping.
1. Connect water supply piping to 1¼" NPT inlet
on unit (piping by installer). Provide adequate
supports (by installer) for supply pipe using pipe
hangers or other means.
2. Connect drain piping to 1¼" NPT drain outlet on
unit (piping by installer).
3. Hang the safety sign from the unit with the
curtain hooks provided (or mount it to the wall
using sign-mounting hardware by installer).
4. Open water supply lines. Test for leaks and
adequate water flow.
4
4/8/2019
25
3
8
(645mm)
4½"
(114mm)
Ø 3.1"
(78.7mm)
(229mm)
86"
(2184mm)
to Bottom
of Base
68½"
(1740mm)
to Bottom
of Base
42"
(1067mm)
to Bottom
of Base
(152mm)
Ø 10"
(254mm)
10½"
(267mm)
Top View From Bowl
All dimensions assume standard thread
engagement. Variations in manufacturing allow
for +/- 1/8" (3mm) per threaded joint. To find
the tolerance of a dimension, add the number
of thread joints in between a dimension and
multiply it by 1/8 (3mm).
Bradley • 215-163 Rev. J; ECO 19-05-003
Installation
"
(2391mm)
to Bottom
9"
66"
(1676mm)
to Bottom
of Base
36
"
3
8
(924mm)
to Bottom
of Base
6"
9½"
(241mm)
Ø 9" (229mm) Flange
with (3) Ø
" (10mm)
3
8
Holes on Ø 8" (203mm)
Bolt Circle
94
"
1
8
of Base

Publicidad

Tabla de contenido
loading