Installation Instructions
SLC 500 Modular Chassis
1746-A4, -A7, -A10, -A13 Series B

Ground Your Chassis

To properly ground your I/O chassis:
verify grounding configuration
install a central ground bus
connect equipment grounding conductor
connect equipment grounding conductor to ground bus
connect ground bus to grounding-electrode system
Verify Grounding Configuration
This figure shows you how to run ground connections from the chassis to the
ground bus. Two acceptable grounding methods are shown; we recommend
using a ground bus because it reduces the electrical resistance at the connection.
2
2 mm
(14 AWG)
2
2 mm
(14 AWG)
2
2 mm
(14 AWG)
6
2
5.2 mm
(10 AWG)
See page:
6
7
7
8
8
Earth Ground
2
5.2 mm
(10 AWG)
Note: Keep wire length
as short as possible.
Preferred Grounding Method