Wiring/Installation
•
Refer to the system installation guide and Lutron job
drawings for power cable and data cable (control
link) wiring restrictions and limitations.
•
Connect the wallstation to the control link inside the
wallstation's wallbox or in a junction box (provided
by others).
•
Use the wire connector required by local code.
Warning! Shock hazard. May result
in serious injury or death. Always turn
OFF the circuit breaker/MCB or remove
the main fuse from the power line before
doing any work.
1. Turn Power OFF. Turn
power OFF at circuit
breaker/MCB (or remove
fuse).
2. Mount Wallbox. Ensure correct size. See
"Mounting" for details.
3. Prepare Wallstations. Remove the faceplate and
set aside.
4. Prepare wires. Strip insulation from wires so that
4 in (10 mm) of bare wire is exposed.
Wire Sizes (check compatibility in your area)
QS Link Wiring Length
Less than 153 m (500 ft)
153 to 610 m
(500 to 2000 ft)
Installation Instructions
LUTRON
Wire Gauge
Power (terminals 1 and 2)
2
1 pair 1.0 mm
(18 AWG)
Data (terminals 3 and 4)
1 twisted, shielded pair 0.5 mm
Power (terminals 1 and 2)
2
1 pair 4.0 mm
(12 AWG)
Data (terminals 3 and 4)
1 twisted, shielded pair 0.5 mm
•
Control link wiring must not be run in the same
raceway as line voltage.
•
The drain/shield wire must be maintained throughout
the control link. Do not connect the shield to earth/
ground or allow contact with the grounded wallbox.
•
Do not connect high-voltage power to low-
voltage ter mi nals. Improper wiring can result in
personal injury or damage to the control or to other
equipment.
Allowable Wiring Configurations
LUTRON
Daisy chain
LUTRON
LUTRON
LUTRON
T-Tap
LUTRON
LUTRON
Wire Strip length
Lutron Cable P/N
GRX-CBL-346S (non-plenum)
GRX-PCBL-346S (plenum)
2
(22 AWG)
GRX-CBL-46L (non-plenum)
GRX-PCBL-46L (plenum)
2
(22 AWG)
4
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
4 in (10 mm)
Occupant Copy