Automatic Correction Of Current Connections - Phoenix Contact EMpro EEM-MA600 Instrucciones De Montaje

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 39
English
U
1 x
3 seconds
Figure 14
Calling the function test
Open edit mode via the ▶ button. Select "YES" or "NO" using ▲ or ▼. Confirm the setting with "OK".
Press and hold down the "test button" again for at least three seconds; the device switches to display mode again.
6.2

Automatic correction of current connections

If the direction of current flow is mixed up due to the connection order being incorrect, the measurement sig-
nals can be corrected automatically. It is not necessary to rewire connection terminal blocks S1 (input) and
S2 (output).
1x
3 seconds
Figure 15
Example: Err 2 – Current transformer connection phase 2
Open edit mode via the ▶ button. Select "YES" or "NO" using ▲ or ▼. Confirm the setting with "OK".
Press and hold down the "test button" again for at least three seconds; the device switches to display mode again.
12 PHOENIX CONTACT
EMpro
104513_en_03