3. Mounting
Panel cut out
4. Electrical connections
View of rear of unit
Measuring- and
X2
control inputs
as well as auxil-
iary signals
X1
Power supply
and limit out-
puts
4.1 Measuring Inputs
Current input
X2
-
+
1
2 3 4 5 6 7 8 9 10 11
1
Current input (I)
0 ... 20 mA / 4 ... 20 mA
2
GND1 (Analogue)
Page 8
Warning: for 90 ... 260 V AC ver-
sion. Please apply the power sup-
ply after the complete installation.
Danger of Death! Please check
unit label before applying the power
supply.
Voltage input
X2
-
+
1
2 3 4 5 6 7 8 9 10 11
2
GND1 (Analogue)
3
Voltage input (U)
0 ... 10 V, 2 ... 10 V, -10 ... +10 V
4.2 Control inputs and auxiliary power supply (U out )
1
1
1
X2
1 2 3 4 5 6 7 8 9 10 11
1 Alternatively connect directly to DC supply
(galvanic separation of control and measure-
ment inputs)
4.3 Power supply and alarm outputs
Relay output
OUT 2
OUT 1
X1
1
2
3 4 5 6 7 8
9
GND3 (for U
)
out
10 Uout +10 V/30 mA
11 Uout +24 V/50 mA only for power
supply 90 ... 260 V AC
8
MP-Input "Reset-Alarm-Latch/
Display-Hold/Reset Totalizer"
7
GND2 (KEY/MPI)
6
Keypad lock-out "Key"
DC voltage
AC voltage
7
10 ... 30 V DC
90 ... 260 V AC (N~)
8
GND4 (0 V DC)
90 ... 260 V AC (L~)
Warning: at 90 ... 260 V AC version.
Please apply the power supply
after the complete installation.
Danger of Death! Please check
unit label before applying the power supply.
Page 9