Technical data - Messaging module CP-C MM
Data at T
= 25
o
C, V
= 230 V AC, if nothing else indicated
A
IN
Type
Technical data
Input
V
Rated input voltage
IN
Input voltage range
Power consumption
"REMOTE OFF" INPUT
Switching-off
Switching-on
Input current
Max. line length
Measuring circuit "INPUT"
Monitoring function
Thresholds
Accuracy, tolerance
Hysteresis, related to the threshold value
Max. measuring cycle
Measuring circuit "OUTPUT"
Monitoring function
Thresholds
Accuracy, tolerance
Hysteresis, related to the threshold value
Max. measuring cycle
OUTPUT circuits
Number of contacts
Operational principle
Contact material
Rated voltage acc. to VDE 0110, IEC 60947-1
Min. switching voltage
Max. switching voltage
Min. switching current
Max. switching current
Rated switching current acc. to IEC
AC 12 (resistive)
AC 15 (indicutive) 230 V
DC 12 (resistive)
DC 13 (indicutive)
Maximum mechanical lifetime
Maximum electrical lifetime
Short circuit proof, max. fuse rating n/c contact
Indication of operational states
green LED "INPUT OK"
green LED "OUTPUT OK"
green LED "REMOTE OFF"
General data
Duty time
Dimensions W x H x D
Weight
Wire size
stranded wire with wire end ferrule
stranded wire without wire end ferrule
solid
stripping length
torque
Degree of protection, enclosure / terminals
Material of enclosure
Protection class
Environmental data
Operating temperature
Storage temperature
Mounting, mounting position
Fastening
Isolation data
Rated insulation voltage acc. to IEC 60947-1,EN 50178,VDE 0160
Supply / measuring circuits / relay outputs
110 - 240 V AC / 100 - 350 V DC, supplied by the input circuit of the power supply
230 V
24 V
24 V
n/o contact
56.5 x 54 x 24 mm / 22.2 x 2.13 x 0.94 inches (when mounted)
CP-C MM
70 - 264 V AC / 80 - 350 V DC
2.5 VA / 1.5 W
volt-free (dry/floating) control
R < 1 kOhm
R > 10 kOhm
typ. 1 mA (200 mA for 200 μs)
25 m
undervoltage monitoring
85 V AC / 90 V DC
- 5 % at AC and DC
typ. -8 % at AC and -30 % at DC
typ. < 50 ms
undervoltage monitoring
20 V DC
+ 1%
typ. 5%
typ. < 10 ms
Relays 11-12/14, 21-22/24
2 x 1 c/o contact
closed-circuit principle
AgNi
250 V
24 V
250 V
10 mA
1 A
1 A
1 A
1 A
1 A
6
30 x 10
switching cycles
6
0.1 x 10
switching cycles
2 A fast acting
2 A fast acting
illuminated, if relay "INPUT OK" energized
illuminated, if relay "OUTPUT OK" energized
illuminated, if "REMOTE OFF" input < 1 kOhm
100%
65 g / 0.14 lb
0.22 - 2.5 mm
2
/ 22 - 14 AWG
0.22 - 2.5 mm
2
/ 22 - 14 AWG
2
0.20 - 4.0 mm
/ 22 - 12 AWG
7.5 mm / 0.295 inches
0.4 - 0.6 Nm
IP 20 / IP 20
UL94V0
II
o
-25
C ... +70
-40
o
C ... +85
plugged onto the power supply unit
snap-on mounting, without any tool
250 V
safe isolation acc. to EN 50178, EN 60950
o
C
o
C
12