8. Heating cycle setting/assembly
04
The heating-cycle setting (CDF value) is for
adapting to the control range.
This is affected by:
– Room size
– Type of heating, e. g. convectors,
storey heating
– Type of assembly
– Temperature control/thermostat
The set value can be altered to achieve
an optimum heating control.
The set value from 1 to 6. If the room-
temperature change is too great (e. g.
caused by ventilation), the cycle time
can be prematurely ended or the unit
can be re-activated.
If the temperature difference in the room
is too great, the system switches ON
and OFF too infrequently.
This means that the CDF value must
be reduced.
If the system switches too frequently,
a higher CDF value must be selected
accordingly.
Factory setting CDF = 4