en
Installation
Purpose
The DOW1171 wireless radio smoke detector (Fig. 1, [2])
is used in conjunction with the FDCW221 radio gateway in
the FS20 fire detection system or in conjunction with the
DCW1151 radio gateway in the AlgoRex fire detection
system.
Up to 30 radio smoke detectors can be connected to a
radio gateway over a maximum distance of 40 m.
The radio smoke detector is screwed into the DBW1171
base (Fig. 1, [1]).
Preparation
Ensure that there is a radio connection between the radio
smoke detector, in its intended installation site, and the
radio gateway.
When determining where to site the base (Fig. 3), ensure
that the alarm indicator [3] can be clearly seen from the
investigation route [4].
Installation
1. Use 2 screws to fit the base on a plane surface (Fig. 4
and Fig. 5). Note the minimum spacing specified (Fig. 2)
and the position of the alarm indicator [5] marked on the
base [1].
2. If necessary, plug a labeled DBZ1193A detector
designation plate (Fig. 4, [6]) into the base [1].
Building Technologies
Fire Safety & Security Products
DOW1171 Radio smoke detector
DBW1171 Base
3. If necessary, insert a detector locking device (Fig. 6, [7])
in the base [1].
A radio smoke detector screwed in the base can only
be unlocked using a screwdriver.
4. Only place the batteries in the radio smoke detector
when commissioning.
Commissioning
When commissioning the radio smoke detector, note the
documents 'FDCW221 Radio gateway', doc. no. 009865,
and 'DCW1151, DOW1171 Wireless fire detection
system', doc.-no. 1787.
Register the radio smoke detector on the radio gateway as
described in doc. no. 009865 and/or 1787.
CE conformity:
Siemens Schweiz AG declares that the DOW1171
radio smoke detector satisfies all CE conformity
requirements.
EMC Dir = 2004/108
The full EC declaration of conformity can be obtained
by calling:
+49 89 9221-8000
3
A6V10200370_a_--_--.doc
05.2008