4.1.2 CHARGER MOUNTING
1.
Remove the cover over the controller in the generator
2.
The battery charger can be located anywhere within the con-
trols area on the generator. It is convenient to mount the char-
ger on the vertical surface on right-hand side of the controller
(Figure 4.3).
Figure 4.3 — Mounting Location of Charger in
Generator
3.
Clean the surface where the charger is to be mounted prior to
mounting with a damp cloth and wait for the area to dry.
4.
Remove the adhesive covering on the backside of the char-
ger and firmly press the charger into place as shown. Once
mounted the charger may be removed for inspection by sepa-
rating the hook & loop mounting (Figure 4.4).
Figure 4.4 — Removal of Adhesive Covering on Hook
and Loop for Mounting
Charger Mounting
Section 4 — GenReady Installation
Battery Charger Installation Guidelines
4.1.3 WIRING AND CONNECTIONS AT THE
GENERATOR
1.
Identify the DC output wires on the battery charger and crimp
spade lugs onto both the positive and negative lead (see
Figure 1.1).
2.
Attach the positive and negative battery charger leads to the
terminal strip in the controller. The positive lead is either a red
wire or is marked with a (+) or (15B) designation. The nega-
tive lead is black and/or marked with a (-) or (0) designation.
The positive lead attaches to the terminal labeled "15B". The
negative lead attaches to the terminal labeled "0". Note that
there will be two wires attached to both the "0" and the "15B"
terminals when the full installation is completed (Figure 4.5).
Figure 4.5 — Connection of Charger DC Output Wires in
Generator Control Panel
3.
Using wire nuts attach the 120VAC input wires from the bat-
tery charger to the generator backed-up 120VAC circuit from
the transfer switch (Figure 4.6).
Figure 4.6 — Connection of charger AC input wires in
generator control panel
7