Ferroli GN2 N Instrucciones De Uso, Instalación Y Mantenimiento página 4

Caldera de fundición, de alto rendimiento para combustibles líquidos y/o gaseosos
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 22
2.1 Water connections
Make the water connections to the appliance according to the indications shown both next to each fi tting and in Figure 2 of this booklet.
The connections must be made in such a way that the pipes are not under stress. The safety valve must be fi tted in the central heating circuit,
as close as possible to the boiler, without there being any obstructions or on-off devices between the boiler and the valve.
The appliance is not supplied with an expansion vessel, and therefore such device must be connected by the installer. Please note that in this
regard, the pressure in the system, when cold, must be between 0.5 and 1 bar.
2.2 Connecting the burner
Oil or gas jet burners for pressurised furnaces can be used if their operating characteristics are suitable for the dimensions of the boiler's
furnace and its over-pressure value. The burner must be chosen following the instructions provided by the manufacturer, according to the fi eld
of operation, fuel consumption and pressure, as well as the length of the combustion chamber.
Fit the burner following the instructions provided by the manufacturer of the device.
2.3 Electrical connections
The boiler should be connected to a single-phase, 230 Volt-50 Hz electrical line, using a permanent connection, installing a double pole switch
with contact openings of at least 3mm, and suitable fuses. Connect the burner and the room thermostat (if featured) as shown in the
wiring diagram in Chap. 4.
The electrical safety of the appliance is ensured only when the appliance is correctly connected to an effective earth system, as
prescribed by the safety standards in force. Have professionally qualifi ed personnel check the effi ciency and the rating of the earth
system. The manufacturer is not liable for any damage caused by the appliance not being correctly earthed. In addition, make sure that the
electrical system is adequately rated for the maximum power absorbed by the appliance, indicated on the rating plate, and in particular that
the cross-section of the wires is suitable for the power absorbed by the appliance.
2.4 Flue connections
The boiler should be connected to a suitable fl ue, manufactured in compliance with the standards in force. The pipe between boiler and the fl ue
must be made from material suitable for this purpose, that is, resistant to both high temperatures and corrosion. The joints should be carefully
sealed and the entire length of the pipe between the boiler and the fl ue should be thermally insulated, to avoid the formation of condensate.
2.5 Assembling the boiler
The boiler may be supplied:
1. As a set of elements, in 4 separate boxes, containing the Casing, Control panel, Elements, and accessories for assembling the elements.
Follow the instructions enclosed with the set of elements to assemble the boiler body. Follow the instructions below to assemble the casing
and control panel.
2. With the body already assembled, in 3 separate boxes containing the Casing, Control panel and Boiler body.
Follow the instructions below to assemble the casing and the control panel.
1
A
L
A
B
1
GN2 N
5
/
604
547
1
GN2 N
6
/
714
657
GN2 N
7
/
824
767
GN2 N
8
/
934
877
GN2 N
1044
604
9
547
1
GN2 N
10
1154
714
657
GN2 N
11
1264
824
767
GN2 N
12
1374
934
877
GN2 N
13
1484
604
547
1
GN2 N
14
1594
714
657
C Prepare the right and left sides, choosing the quantity of side panels according to the dimensions of the boiler (see table).
4
A If the boiler body is supplied already
2
B Fit the rear panel 1 on the studs 2 and
2
1
2
2
B
Quantity
Cover
R side
L side
type
type
type
2
3
4
5
1
2
3
4
1
2
3
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
2
1
1
1
1
2
1
1
1
1
2
2
1
1
4
C
1
2
1
1
4
cod. 3541A581 - Rev. 02 - 03/2018
assembled and is delivered from the
factory on a pallet, remove the bolts 1
that fasten it to the pallet and position
it for fi nal installation. Then assemble
the various panels.
loosely tighten the bolts.
L
A
440
B
Cover type 5
Cover type 1, 2, 3 e 4
Reversible
R and L sides
side
Type: 1,2,3,4
Version 9-12 Elements
GN2 N
A
B
Cover type 1, 2, 3 e 4
R and L sides
Type: 1,2,3,4
Version 5-8 Elements
L
440
440
57
Cover type 5
Cover type 5
Cover type 1, 2, 3 e 4
Reversible
Reversible
R and L sides
side
side
Type: 1,2,3,4
Version 13-14 Elements
57
A
B
57

Publicidad

Tabla de contenido
loading

Tabla de contenido