2° Set "Current %" trimmer to 60% since:
I% =
having wired terminals 7 - 12.
3° Set "Hysteresis %" trimmer (tripping window) to 10% to
obtain a tripping window of 6 to 6.6 A (6 A + 10% = 6.6 A):
the relay will trip at 6 A and regular operation will start again
at 6.6 A.
4° Set the "Delay" trimmer
This makes it possible to delay the relay tripping time (1.... 30
sec). (During the delay the "Power on" LED will flash; at the
end of the delay the "Alarm" LED will turn on and the relay will
trip).
I
=7A
n
6,6A
I
=6A
min
6 (I
)
min.
x 100 = 60%
10 (I
)
limit
Alarm
In allarme
condition
Regular
Normale
funzionamento
operation
No alarm because
Non in allarme perchè fuori
outside of hysteresis
dalla finestra di isteresi
window
Still in alarm because within
In allarme in quanto all'interno
della finestra di isteresi
the hysteresis window
Selected
Finestra
hysteresis
di isteresi scelta
window = 10%
= 10%