To be sure that starting relay will function and
that overload will not "nuisance trip", install
control box vertically with top side up.
Wire control box as shown in Figures 1A and 1B .
A 3-wire pump will not operate without control
box. Operation without control box will burn out
3 wire motor.
Installation must include circuit and component
protection which meet local code and United
States National Electrical Code requirements.
If main overload trips, look for:
1.
Shorted Capacitor
2.
Voltage Problems
3.
Overloaded or locked pump.
NOTICE Match motor to control box as shown
below.
TABLE IV: Control Box Selection
HP
Voltage
Motor No.
1/2
115
G43A0005A1
1/2
230
G43A0005A2
3/4
230
G43A0007A2
1
230
G43A0010A2
1-1/2
230
G43A0015A2
NOTICE Control box included in package with
3-wire pump assembly must be used or war-
ranty is void.
For parts or assistance, call Simer Customer Service at 1-800-468-7867 / 1-800-546-7867
For parts or assistance, call Simer Customer Service at 1-800-468-7867 / 1-800-546-7867
All manuals and user guides at all-guides.com
Control Box No.
FIGuRE 1A - 3-wire quick disconnect box. Follow
74182R
color coding when connecting control box (Yellow to
Y, Red to R, Black to B).
2876G
2886G
2896G
SMC-CR1521-02
FIGuRE 1B - Single phase, 2-wire connections. 2-wire
pumps have two power supply wire (Black) and one
ground wire (Green). Control box is not required. This
is correct connection information for 115 and 230 volt
2-wire motors only.
4