Combinations With Corresponding Led And Relay Status - Dräger Polytron 8100 Instrucciones De Uso

Ocultar thumbs Ver también para Polytron 8100:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 128
Menu
5.7.3

Combinations with corresponding LED and relay status:

Combination(s)
Diagram
Case: Alarm is acknowledged before the alarm condition cleared.
Latching
Acknowledgeable
Non-latching
Acknowledgeable
Case: Alarm is acknowledged after the alarm condition cleared.
Latching
Acknowledgeable
Latching
Pre-acknowledgeable
Latching
Non-acknowledgeable
Case: Alarm is acknowledged before the alarm condition cleared.
Latching
Pre-acknowledgeable
Non-latching
Pre-acknowledgeable
Case: Alarm is not acknowledged.
Non-latching
Non-acknowledgeable
Non-latching
Acknowledgable,
20
a
b
c
d
1
2 3
a
b
c
d
1
2
3
a
b
c
d
1
2
3
a
b
c
d
1
2
Relay (if a realy board is installed), LED, and symbol status
1 Alarm condition is present.
Relay (b) is energized and symbol (b) is active.
LED (c) starts flashing.
2 Alarm condition is acknowledged (d) but is still present.
Relay (b) and symbol (b) are reset.
LED (c) is lit continously to indicate the present alarm condition.
3 Alarm condition clears.
LED (c) is off.
1 Alarm condition is present.
Relay (b) is energized and symbol (b) is active.
LED (c) starts flashing.
2 Alarm condition clears.
Relay (b) stays energized and symbol (b) stays active.
LED (c) keeps flashing.
3 Alarm is acknowledged (d)
Relay (b) and symbol (b) are reset
LED (c) is off.
1 Alarm condition is present.
Relay (b) is energized and symbol (b) is active.
LED (c) starts flashing
2 Alarm is about to be acknowledged (d), but acknowledging is not
possible.
Relay (b) stays energized and symbol (b) stays active.
LED (c) is continuously lit.
3 Alarm condition cleared.
Relay (b) and symbol (b) are reset without acknowledging.
LED (c) is off without acknowledging.
1 Alarm condition is present.
Relay (b) is energized and symbol (b) is active.
LED (c) starts flashing.
2 Alarm condition cleared.
Relay (b) and symbol (b) are reset without acknowledging.
LED (c) is off without acknowledging.
Dräger Polytron 8100

Publicidad

Tabla de contenido
loading

Tabla de contenido