Installation Instructions: 655/675LR and K655/K675LR
CONTENTS:
Elbow, Cable Adapter, Compression Lug, Insulating Plug, Lubricant, Stud Prepack, Crimp chart,
Installation Instructions.
The 655/675LR and K655/K675LR connectors are designed to: 1) provide fully shielded, fully submersible deadfront cable
connections to high voltage apparatus and 2) provide a means to splice and tap 600--ampere (655/K655LR) or 900--ampere
(675/K675LR) systems. The connectors are rated for use on 15kV and 25kV class systems respectively.
All apparatus must be de- -energized during installation
or removal of part(s).
Do not touch or move energized products in the work
area.
These instructions do not attempt to provide for every
possible contingency.
Failure to follow these instructions will result in
damage to the product and serious or fatal injury.
This product should be installed only by competent
personnel trained in good safety practices involving
high voltage electrical equipment. These instructions
are not intended as a substitute for adequate training or
experience in such safety practices.
FOR MORE INFORMATION ON PARTS, INSTALLATION RATINGS AND COMPATIBILITY, CALL THE NEAREST ELASTIMOLD
Limited Warranty:
1. T&B warrants that its products will be free from defects in materials or workmanship for a period of two (2) years, except
for tools which are warranted separately (see warranty accompanying those products). Fisher Pierce products and
Elastimold Reclosers are warranted for three years; and Joslyn™ VBT and VBU capacitor switches are warranted for
four years or 40,000 operations whichever occurs first. Upon prompt notification of a warranted defect, T&B will, at its
option, repair or replace the defective product.
2. In no event shall T&B be liable for any consequential, indirect or special damages, nor will T&B be liable for
transportation, labor, or other charges arising out of the removal or reinstallation of its products. Liability for breach of
warranty is limited to the cost of repair or replacement of the warranted product only.
3. Misuse, misapplication or modification of T&B products immediately voids all warranties.
THE WARRANTIES AND REMEDIES CONTAINED HEREIN ARE EXCLUSIVE AND ARE IN LIEU OF ALL OTHER
WARRANTIES AND REMEDIES, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE, WHICH ARE SPECIFICALLY DISCLAIMED.
1. Check contents of package to ensure they are complete
and undamaged.
2. Check all components to ensure proper fit with cable
and/or mating products.
IS---0249
IS---655/675LR & K655/K675LR
March 2016
Printed in U.S.A.
Deadbreak Elbow Connectors
IMPORTANT
8155 T&B Boulevard, Memphis, Tennessee 38125
(800) 888- -0211 Fax: (800) 888- -0690
DANGER
All apparatus must be installed and operated in
accordance with individual user, local, national work
rules and electrical standards.
For loadbreak products follow operating instructions.
All deadbreak connectors must be de- -energized before
operating. All 200A deadbreak connectors must be
mechanically secured with bails when connected.
If this product is supplied with a protective shipping
cover(s), remove this shipping cover(s) and replace
with
the
appropriate
connector(s) before submerging or energizing the
circuit.
Inspect parts for damage, rating and compatibility with
mating parts.
Excess distortion of the assembled product may result
in its failure.
3. Read entire installation instructions before starting.
4. Have all required tools at hand and maintain cleanliness
throughout the procedure.
IS---0249
IS- - 655/675LR & K655/K675LR
March 2016
Page 1 of 10
(English: pages 1 through 5)
(Español: páginas 6 mediante 10)
HV
insulated
cap(s)
R
OFFICE.
or