CHECKING THE INITIAL CONFIGURATION
Check the following items:
1.
AC unit-system communication: Set the Airzone system to an operation mode other
than Stop and turn on the zone to generate demand. Verify that the mode imposed on
the master thermostat appears on the indoor unit thermostat and that the set-point
temperature changes on the same.
2.
AC unit-system communication: Set the Airzone system to Stop mode and verify that the
AC unit turns off and dampers open.
3.
Opening/closing of the dampers and control outputs: Turn on and generate demand in
all the zones. Then turn each zone off and on to check that the associated control outputs
are correct.
4.
Check that the static pressure in the ducted AC unit is in accordance with the conditions of
the airflow distribution network in which it is installed (see the manufacturer's manual for
the AC unit if you need to modify this parameter).
SYSTEM RESET
If you need to return the system to factory
settings, press and hold SW1 until LED D19
stops blinking. Wait for the LEDs to return
to their normal status and then repeat the
initial configuration.
ZONE RESET
For Blueface and Think thermostats, follow the steps indicated in the Advanced settings menu,
Zone parameters.
For Lite thermostats, lower all microswitches and replace the thermostat in its base. The icon
will blink twice in green confirming that the reset has been completed.
EN
SW1
15