SYSTEM PARAMETERS

System address. (Not available on systems with BACnet gateway). This allows you to define
the number of the system in your installation. By default, it displays the value 1. The system
will show the free address values with a maximum value of 99.
If you have address 1 and have an Airzone production control board (AZX6CCP /
AZX6CCPWSCC) in the installation, you can use the Supermaster function, which imposes
the operation mode of system 1 on the other systems connected to the AZX6CCP /
AZX6CCPWSCC in a semi-forced way:
EN
Temperature range. This allows you to select the maximum temperature for heating mode
(19-30°C) and minimum temperature for cooling mode (18-26°C), in steps of 1°C. If you want,
you can disable any of the modes. By default, the maximum heating temperature is set to
30°C and the minimum cooling temperature to 18°C.
Combined stage. (Only available in installations with AZCE6OUTPUT8 modules). This
allows you to activate/deactivate the combined stage of the "Control stages" parameter in
the user "Zone settings" menu.
Hysteresis
temperature and the set-point temperature to begin to apply the RadianT algorithm, which
aims to prevent underfloor heating installations overheating. In installations with radiators,
set this value to 0°C. By default, it is set to 0°C.
Type of opening*. This allows you to enable/disable the proportionality of the system
dampers. Proportionality scales the opening or closing of the damper in 4 steps according
to the temperature demand of the zone, adjusting the zone airflow rate. By default, it is set
to All/Nothing.
*Note: Changing this parameter affects all motorized dampers in the installation. It is not
recommended for RINT and RIC smart grilles.
Standby mode. (Only for Airzone Blueface thermostats). Configuration of the operation
logic of the motorized elements when there is no demand on the system. This is disabled by
default.
Relay settings. This allows you to change the operation logic of the main control board's
CMV/Boiler relay. By default, it is set to CMV.
18
Operation mode of system 1
Config.
This defines the temperature differential between the room
Available operation modes of the
other systems